Reference Manual

Reference Manual
00809-0100-4102, Rev AA
Section2:Configuration
May 2013
Configuration
24
2051 Wireless pressure transmitter, damping only takes effect when the device is placed in high
power refresh mode and during calibration. In normal power mode, the effective damping is 0.
Note that when the device is in high power refresh mode, battery power will be depleted rapidly.
Determine the appropriate damp setting based on the necessary response time, signal stability,
and other requirements of the loop dynamics of your system. The damping value of your device
is user selectable from 0 to 60 seconds.
DampingwithaFieldCommunicator
From the HOMEscreen, enter the fast key sequence
Enter desired Damping Value and select APPLY.
DampingwithAMSDeviceManager
Right click on the device and select Configure.
1.
Select
ManualSetup
.
2.
Within the PressureSetupbox, enter desired damping value and click Send.
3.
Carefully read the warning and click Yesif it is safe to apply the changes.
2.9.3
Write protect
The Rosemount 2051 Wireless pressure transmitter has a software write protect security
feature.
EnablingwriteprotectwithaFieldCommunicator
From the HOMEscreen, enter the fast key sequence
Select WriteProtectto enable.
EnablingwriteprotectwithAMSDeviceManager
Right click on device and select Configure.
1.
Select
ManualSetup.
2.
Select the tab labeled DeviceInformation.
3.
Select WriteProtectto enable this feature.
2.10
Diagnosticsandservice
Diagnostics and service functions listed below are primarily for use after field installation. The
Transmitter Test feature is designed to verify that the transmitter is operating properly, and can
be performed either on the bench or in the field.
DeviceDashboardFastKeys
2, 2, 7, 1
DeviceDashboardFastKeys
2, 2, 2, 4