Diagnostics (ADB) Transducer Block
TABLE 11-3. Plugged Impulse Line
Parameters
Parameter Index Units Description
PLINE_STATUS 878 NA Last Impulse line status
PLINE_TIMESTAMP 879 Last Timestamp for PLINE_STATUS
PLINE_ON 880 NA Turns algorithm on/off
PLINE_RELEARN 881 NA Resets the algorithm and reinitiates
learning
PLINE_SENSITIVITY 882 NA Detection sensitivity
PLINE_AFFECT_PV_STATUS 883 NA Determines whether the quality of
the pressure measurement will be
affected or unaffected
PLINE_HISTORY_STATUS 884 NA Last plugged line determination
status
PLINE_HISTORY_TIMESTAMP 885 Last plugged line determination
timestamp
PLINE_LEARN_LENGTH 886 Min Length of learning and verification
cycles in minutes
PLINE_DETECT_LENGTH 887 Min Length of detection cycle status
update in minutes
PLINE_AUTO_RELEARN 888 Enables/disables auto relearn on
process mean changes
PLINE_RELEARN_THRESHOLD 889 %URL Threshold for relearning in%URL of
sensor (excludes Range 1 and 2
DP... Those thresholds are fixed at 2
and 5 inH20)
PLINE_LEARN_SENSITIVITY 890 Learning sensitivity check options.
Only one of bits 2,3, and 4 is
allowed and only one of bits 5 and 6
is allowed.
PLINE_DETECT_SENSITIVITY 891 % Overrides IL Plugging sensitivity if a
non-zero value is entered. Value
corresponds to a percentage
decrease in standard deviation.