Owner's manual
Table Of Contents
- Foundation™ Fieldbus Blocks
- Foundation™ Fieldbus Technology and Fieldbus FunctionBlocks
- Analog Input (AI) FunctionBlock
- Analog Output (AO) Function Block
- Arithmetic Function Block
- Discrete Input (DI) Function Block
- Discrete Output (DO) Function Block
- Integrator (INT) FunctionBlock
- Input Selector (ISEL) FunctionBlock
- Proportional/Integral/Derivative (PID) Function Block
- Signal Characterizer (SGCR) Function Block
- Diagnostics (ADB) Transducer Block
- Applications
- Analog input (AI) Function Block
- Analog Output (AO) Function Block
- Arithmetic (ARTH) Function Block
- Discrete Input (DI) Function Block
- Discrete Output (DO) Function Block
- Input Selector (ISEL) Function Block
- Integrator (INT) Function Block
- Proportional/ Integral/Derivative (PID) Function Block
- Signal Characterizer (SGCR) Function Block
- Index

Section
7-1
7 Integrator (INT) Function Block
The Integrator (INT) function block integrates one or two variables over
time. The block compares the integrated or accumulated value to
pre-trip and trip limits and generates discrete output signals when the
limits are reached.
The Integrator function block supports mode control, demand reset, a
reset counter, and signal status calculation. There is no process alarm
detection in the block. Figure 7-1 illustrates the internal components of
the INT function block, and Table 7-1 lists the system parameters.
IN_1 = The first input value and status.
IN_2 = The second input value and status.
REV_FLOW1 = The discrete input that specifies
whether IN_1 is positive or negative.
REV_FLOW2 = The discrete input that specifies
whether IN_1 is positive or negative.
RESET_IN = The discrete input that resets the
integrator and holds reset until released.
OUT = The integration output value and
status.
OUT_PTRIP = A discrete value that is set when the
pre-trip limit value is reached.
OUT_TRIP = A discrete value that is set when the
trip target value (setpoint) is reached.
N_RESET = The number of times the integrator
function block is initialized or reset.
INT
OUT
OUT_PTRIP
IN_1
IN_2
REV_FLOW1
REV_FLOW2
RESET_IN
OUT_TRIP
N_RESET
FIELDBUS-FBUS_35A