Status Handling Output or readback fault detection are reflected in the status of PV,
OUT, and BKCAL_OUT. A limited SP condition is reflected in the
BKCAL_OUT status. When simulation is enabled through the
SIMULATE attribute, you can set the value and status for PV and
READBACK.
When the block is in Cas mode and the CAS_IN input goes bad, the
block sheds mode to the next permitted mode.