Reference Manual 00809-0600-4410, Rev AA May 2020 Emerson Wireless 1410S Gateway and 781S Smart Antenna
Reference Manual 00809-0600-4410 Contents May 2020 Contents Chapter 1 Introduction.............................................................................................................. 5 1.1 Emerson Wireless 1410S Gateway 781S Smart Antenna.............................................................. 5 1.2 Using this manual........................................................................................................................ 5 1.3 Product recycling/disposal......................
Contents May 2020 Reference Manual 00809-0600-4410 6.9 AMS Wireless Configurator: Device configuration items are grayed out..................................... 47 6.10 Wireless field devices: Wireless device does not appear on the network.................................. 48 6.11 Wireless field devices: Wireless device appears in the join failure list........................................ 48 6.12 Wireless field devices: Wireless device appears with service denied........................................
Reference Manual 00809-0600-4410 Introduction May 2020 1 Introduction 1.1 Emerson Wireless 1410S Gateway 781S Smart Antenna The Emerson Wireless 1410S Gateway and 781 Smart Antenna combine to create the main access point of a wireless network. Modbus® communications over RS-485 or Ethernet provide universal integration and system interoperability.
Introduction May 2020 6 Reference Manual 00809-0600-4410 Emerson.
Reference Manual 00809-0600-4410 Configuration May 2020 2 Configuration 2.1 Wireless planning Power up sequences The Gateway should be installed and functioning properly before power modules are installed in any wireless field devices. Wireless field devices should also be powered up in order of proximity from the Gateway beginning with the closest. This will result in a simpler and faster network installation.
Configuration May 2020 Reference Manual 00809-0600-4410 Gateway are operationally equivalent and the following instructions are applicable to both. Powering the Gateway For the Emerson 1410S, bench top power will be needed to power the Gateway by wiring a 10.5–30 VDC (24 VDC if configured with I.S. barriers) power source. See Power specifications for power requirements or Reference data for specifications. Figure 2-1: Emerson 1410S Gateway Wiring A. B. C. D. E. F.
Reference Manual 00809-0600-4410 2.3.2 Configuration May 2020 Windows 7 Procedure 1. Click the Internet Access icon on the bottom right of the screen. 2. Select the Network and Sharing Center. 3. Select Local Area Connection. 4. Select Properties. 5. Select Internet Protocol Version 4 (TCP/IPv4) → Properties.
Configuration May 2020 Reference Manual 00809-0600-4410 Note If the PC/laptop is from another network, record the current IP address and other settings so the PC/laptop can be returned to the original network after the Gateway has been configured. 6. Select the Use the following IP address button. 7. In the IP address field, enter 192.168.1.12 (DeltaV Ready enter 10.5.255.12). 8. In the Subnet mask field, enter 255.255.255.0. 9.
Reference Manual 00809-0600-4410 Configuration May 2020 3. Select Change adapter options.
Configuration May 2020 Reference Manual 00809-0600-4410 4. Right click the network interface connection that the Gateway is plugged into, and select Properties. 5. Select Internet Protocol Version 4 (TCP/IPv4) → Properties. Note If the PC/laptop is from another network, record the current IP address and other settings so the PC/laptop can be returned to the original network after the Gateway has been configured. 6. Select the Use the following IP address button. 12 Emerson.
Reference Manual 00809-0600-4410 Configuration May 2020 7. In the IP address field, enter 192.168.1.11 (DeltaV Ready enter 10.5.255.12). 8. In the Subnet mask field, enter 255.255.255.0. 9. Select OK for both the Internet Protocol (TCP/IP) Properties window and the Local Area Connection Properties window. Note Connecting to the Gateway's secondary Ethernet port will require different network settings. Table 2-1: Network Settings 2.3.4 Ethernet Gateway PC/laptop/tablet Subnet 1 192.168.1.10 192.
Configuration May 2020 Reference Manual 00809-0600-4410 3. Under Proxy server, uncheck the Use a proxy server... box. 2.3.5 Configure the Gateway Use these steps to complete the initial configuration for the Gateway. This will need to be done for both the WirelessHART® and ISA100 networks. Procedure 1. Access the WirelessHART default web page for the Gateway at https:// 192.168.1.10. You will have to configure both networks individually.
Reference Manual 00809-0600-4410 Configuration May 2020 2. Navigate to System Settings → Gateway → Ethernet Communication to enter the network settings. a) Configure a static IP Address or set for DHCP and enter a Hostname. b) If not prompted, restart application at System Settings → Gateway → Backup and Restore → Restart Apps. Note Resetting applications will temporarily disable communications with field devices. 2.3.
Configuration May 2020 Reference Manual 00809-0600-4410 Figure 2-2: User Privileges 2.3.7 Change passwords It is a secure practice to change the user account passwords from the default ones. This should be done on both the WirelessHART and ISA10 networks. To change the User Account passwords, follow the steps below. Procedure 1. Navigate to System Settings → Users → User Accounts. 2. Click the Edit button of the user password to be changed. 3.
Reference Manual 00809-0600-4410 2.3.8 Configuration May 2020 Time settings The Gateway is the timekeeper for the WirelessHART® network, so it is imperative that the Gateway’s time is accurate for timestamp data to be meaningful. Time settings can be found by navigating to System Settings → Gateway → Time as shown in Windows 7. Any changes made to the time settings will have to be done to both networks for consistency. There are three ways to set the Gateway time: Procedure 1.
Configuration May 2020 Reference Manual 00809-0600-4410 2. Select Specify an IP address (recommended). 3. Enter the following: • Hostname • Domain name • IP Address • Netmask • Gateway 4. Select Save Changes. 5. When prompted, select Restart Apps. 6. Select Yes to confirm restart. 7. Close the web browser. Note Once the IP Address of the Gateway has been changed, communications to the web interface will be lost.
Reference Manual 00809-0600-4410 2.3.11 Configuration May 2020 Web page usage It is not recommended that users stay logged on to a single page or a large number of users on multiple pages for long periods of time. This additional loading can slow the flow of data. By default, he Gateway logs users out after a long period of time with no activity. 2.3.
Configuration May 2020 20 Reference Manual 00809-0600-4410 Emerson.
Reference Manual 00809-0600-4410 Installing the Gateway May 2020 3 Installing the Gateway 3.1 Emerson 1410S1 installation overview This section describes how to properly mount the Gateway and make electrical connections including wiring, grounding, and host system connections.
Installing the Gateway May 2020 3.3 Reference Manual 00809-0600-4410 Power specifications Table 3-1: Emerson 1410S Gateway Power Gateway version Non-barrier Barrier Input voltage 10.5 to 30V VDC 24 VDC Power consumption 5 Watts 7.5 Watts At start-up, the power supply must be capable of momentarily sourcing at least twice the operating current. The Gateway may draw significantly more current momentarily at start-up if not limited by the power supply.
Reference Manual 00809-0600-4410 3.4 Installing the Gateway May 2020 Mounting the Emerson 1410S2 Gateway Find a location where the Gateway has convenient access to the host system network (process control network). 3.4.1 Pipe mount Pipe mount The following hardware and tools are needed to mount the Gateway to a 2-in. pipe: • Two 5/16-in. u-bolts (supplied with Gateway) • 2-in. mounting pipe • ½-in. socket-head wrench Figure 3-1: Pipe Mount 3.4.
Installing the Gateway May 2020 Reference Manual 00809-0600-4410 Procedure 1. Drill four 3/8-in. (9,525 mm) holes spaced 3.06-in. (77 mm) apart horizontally and 11.15-in. (283 mm) apart vertically in the support bracket, corresponding with the holes on the Gateway mounting bracket. 2. Using a 1/2-in. socket-head wrench, attach the Gateway to the support bracket with four 15/16-in. bolts. 3.
Reference Manual 00809-0600-4410 Installing the Gateway May 2020 Figure 3-3: Mounting Location A. B. C. D. E. 3.5.1 Control room Ground Smart Antenna Mast or pipe Infrastructure Emerson Smart Antenna pipe mount Procedure 1. Insert U-bolt around 2-in. pipe/mast, through the saddle, through the L-shaped bracket, and through the washer plate. 2. Use a ½-in. socket-head wrench to fasten the nuts to the U-bolt. 3. Insert single bolt through L-shaped bracket into the antenna. 4.
Installing the Gateway May 2020 Reference Manual 00809-0600-4410 provide intrinsic safety and approval for Emerson 781S installation in Div 1/Zone 0 areas. For more information on product approvals, see Reference data. The Gateway enclosure acts as a junction box for wiring connections. The enclosure has five conduit entries for power and communications wiring. Do not run communication near heavy electrical equipment. Install the included conduit plugs in any unused conduit openings.
Reference Manual 00809-0600-4410 3.6.3 Installing the Gateway May 2020 Emerson 781S installation A shielded twisted-pair cable is needed for connecting the Emerson 1410S and each 781S Smart Antennas. Each Emerson 781S can be located up to 1312 ft. (400m) from the Emerson 1410S. Figure 3-4: Emerson 1410S Gateway and Single 781S Smart Antenna A. B. C. D.
Installing the Gateway May 2020 Reference Manual 00809-0600-4410 Figure 3-5: Emerson 1410S Gateway and Two 781S Smart Antennas A. B. C. D. E. 3.6.4 Emerson Wireless 781S Smart Antenna Attach shield pair cable (Belden 3084A or equivalent) Emerson Wireless 781S Smart Antenna Tape back shield wire and foils Emerson Wireless 1410S Gateway RS-485 The Gateway can be ordered with an optional RS-485 (serial) connection (see Figure 3-4. Modbus® terminals are labeled A and B on the wiring diagram.
Reference Manual 00809-0600-4410 3.6.5 Installing the Gateway May 2020 Shield grounding The shields of the twisted-pair cables need to be grounded using the grounding terminal on the Emerson 1410S, and it should be taped back on the Emerson 781S side. 3.6.6 Terminating resistors Five DIP switches are provided to enable various terminating resistors to the RS-485 (Modbus®) data bus.
Installing the Gateway May 2020 Reference Manual 00809-0600-4410 Figure 3-7: RS-485 Resistor DIP Switches A. B. C. D. E. F. G. H. I. J. K. Input terminal connection Ethernet Port 1 Ethernet Port 2 Terminal connection 1 Terminal connection 2 DIP Switches PoE disabled Reset to defaults 1.5 kΩ pull-down resistor 120 Ω terminating resistor 1.5 kΩ pull-up resistor Switches 1 and 3 are connected to pull-up and pull-down resistors for Modbus connection.
Reference Manual 00809-0600-4410 3.6.7 Installing the Gateway May 2020 Power over Ethernet (PoE) This Gateway is equipped with PoE technology to derive its power from another PoE device via the Ethernet connection (PD mode). This device complies with the IEEE 802.3af-2003 or IEEE 802.3at -2009 for PD operation. These standards require the use of Category 5 Ethernet cable or higher. In the operation of IEEE 802.
Installing the Gateway May 2020 Reference Manual 00809-0600-4410 NOTICE IEEE 802.3 PoE gives protection from damaging a computer or another piece of equipment When using IEEE 802.3 PoE, one of the important new features of this standard is that PSE devices have a test mechanism to protect connected incompatible devices from being damaged. Only devices which have an authenticating characteristic based on the IEEE 802.3 standard, receive power via the Ethernet cable.
Reference Manual 00809-0600-4410 Installing the Gateway May 2020 Figure 3-8: Gateway Log In Screen The Gateway is now ready to be integrated into the host system. If wireless field devices were ordered with the Gateway, they were preconfigured with the same Network ID and Join Key information. Once the field devices are powered, they will appear on the wireless network and communications can be verified under the Explore tab using the web interface.
Installing the Gateway May 2020 34 Reference Manual 00809-0600-4410 Emerson.
Reference Manual 00809-0600-4410 Commissioning May 2020 4 Commissioning 4.1 Overview This section discusses the installation and setup of the optional software included with the Emerson Wireless Gateway. The following table describes what items are installed and on which disk they can be found. Table 4-1: Software Applications Name Description Location Security Setup Utility This utility allows the setup of SSL enabled communications between the Gateway and host system.
Commissioning May 2020 Reference Manual 00809-0600-4410 Table 4-3: Supported Operating Systems (continued) Operating system Version Windows 7 Enterprise, Service Pack 1 Windows 8 Enterprise, Service Pack 1 Windows Server 2008 Standard, Service Pack 2 Windows 10 Enterprise, Service Pack 1 Note Only 32-bit versions of the operating systems are supported for AMS Wireless Configurator. 4.3 Software installation The software can be found on the two-disk pack, included with the Gateway.
Reference Manual 00809-0600-4410 Commissioning May 2020 Security Setup Utility. These proxies can function as a data server for other applications on the control network. The Security Setup Utility can support multiple Gateways at once and each proxy can support multiple client application connects. Figure 4-1 shows a typical system architecture using the Security Setup Utility.
Commissioning May 2020 Reference Manual 00809-0600-4410 • Provision a wireless device using the drag-and-drop operation so it can join a Gateway’s self-organizing network • Enhance AMS Wireless Configurator functionality with the AMS Wireless SNAP-ON™ Application • Restrict access to AMS Wireless Configurator functions through the use of security permissions See the release notes for information specific to the current release of AMS Wireless Configurator.
Reference Manual 00809-0600-4410 Operation and maintenance May 2020 5 Operation and maintenance 5.1 Overview This section describes how to connect the Gateway to a host system and integrate data gathered from the field device network. It covers network architectures, security, and data mapping. 5.2 Network architecture Physical connection types are important when determining the network architecture and usable protocols for integration.
Operation and maintenance May 2020 Reference Manual 00809-0600-4410 RS485 (serial) An RS485 connection supports Modbus RTU protocol. Using this connection type, the Gateway is wired to an RS485 bus which typically leads to a serial I/O card or Modbus I/O card (see Figure 5-2). Up to 31 Gateways can be connected to a single I/O card in this manner. Figure 5-2: RS485 Architecture A. B. C. D. E. F. G. 5.
Reference Manual 00809-0600-4410 Operation and maintenance May 2020 Figure 5-3: Modbus Communications Page Emerson 1410S/781S Single Modbus Address When selected, this address is used by the Gateway for Modbus RTU communications. Multiple Modbus Addresses When selected, a new address column will appear on the Modbus mapping page. Modbus TCP Port This is the TCP/IP port the Gateway uses for Modbus TCP (Ethernet). To change TCP/IP port settings, see the Internal Firewall section for more details.
Operation and maintenance May 2020 Reference Manual 00809-0600-4410 Response delay time This setting determines how long (ms) the Gateway waits before (ms) responding to a Modbus request. This setting is only required for Modbus RTU. Unmapped register read response? This is the value returned by the Gateway if the Modbus master requests a register with no data assigned to it (empty register). It is recommended this be set to zero fill to prevent errors.
Reference Manual 00809-0600-4410 Emerson 1410S/781S Operation and maintenance May 2020 Global scale gain This value is multiplied by the data values for the purpose of scaling integers. If global scaling is not selected, a gain value will be available for each separate data value on the Modbus Mapping page. Global scale offset This value is added to the data values for the purpose of scaling integers.
Operation and maintenance May 2020 44 Reference Manual 00809-0600-4410 Emerson.
Reference Manual 00809-0600-4410 Troubleshooting May 2020 6 Troubleshooting 6.1 Service support This section provides basic troubleshooting tips for the Emerson Smart Wireless Field Network.
Troubleshooting May 2020 6.3 Reference Manual 00809-0600-4410 Initial connection: Cannot find Gateway after changing IP address Possible cause: Incorrect IP address Recommended actions 1. Verify the IP address of the PC/laptop is in the same subnet range as the Gateway (i.e. If Gateway IP address is 155.177.0.xxx, then PC/laptop IP address should be 155.177.0.yyy). 2. Consider resetting the gateway to factory defaults. 6.
Reference Manual 00809-0600-4410 Troubleshooting May 2020 Possible cause: Wireless network interface configuration Recommended actions 1. Verify the Security Setup Utility is installed on the same PC as AMS Wireless Configurator. 2. Setup a wireless network interface using the Network Configuration application. 3. Verify the wireless network interface is configured for secure Gateway communications. 4. Verify secure/unsecure AMS Wireless Configurator protocol settings in the Gateway.
Troubleshooting May 2020 Reference Manual 00809-0600-4410 Possible cause: Session timeout Recommended actions 1. Verify whether current or historical information is being displayed (setting is displayed at the bottom of each device configuration screen). Configuration requires the Current setting. 2. Log back into AMS Wireless Configurator. For security purposes, a configuration timeout is applied to sessions that have been idle for more than 30 minutes. 6.
Reference Manual 00809-0600-4410 6.13 Troubleshooting May 2020 Modbus communications: Cannot communicate using Modbus® RTU Recommended actions 1. Verify the use of RS-485. 2. Verify wiring connections. 3. Verify if termination or a pull up is required. a) Verify that Modbus serial communications settings in the Gateway match the Modbus Host settings. b) Log on to the Gateway and navigate to SETUP → MODBUS → COMMUNICATIONS. 4. Verify the Modbus address for the Gateway. 5.
Troubleshooting May 2020 Reference Manual 00809-0600-4410 Recommended actions 1. Verify the Security Setup Utility has been installed. 2. Configure a secure Modbus proxy for the Gateway (see Security setup utility). 3. Verify secure/unsecure Modbus protocol settings in the Gateway a) Log on to the Gateway. b) Navigate to SETUP → SECURITY → PROTOCOLS. 4. Verify the Modbus TCP communications settings in the Gateway. a) Log on to the Gateway. b) Navigate to SETUP → MODBUS → COMMUNICATIONS. 5.
Reference Manual 00809-0600-4410 Troubleshooting May 2020 Possible cause: Configuration or settings Recommended actions 1. Configure the Gateway OPC Browse Tree. a) Log on to the Gateway. b) Navigate to SETUP → OPC → OPC BROWSE TREE. 2. Verify the connection status for the OPC proxy in the Security Setup Utility. 3. Check to ensure the OPC proxy is configured for secure or unsecure communications. 4. Verify secure/unsecure OPC protocol settings in the Gateway. a) Log on to the Gateway.
Troubleshooting May 2020 Reference Manual 00809-0600-4410 WARNING Individuals who handle products exposed to a hazardous substance can avoid injury if they are informed of, and understand, the hazard. If the product being returned was exposed to a hazardous substance as defined by OSHA, a copy of the required Material Safety Data Sheet (MSDS) for each hazardous substance identified must be included with the returned goods. 52 Emerson.
Reference Manual 00809-0600-4410 Reference data May 2020 A Reference data A.1 Ordering information, specifications, and drawings To view current Emerson 1410S and 781S ordering information, specifications, and drawings, follow these steps: Procedure 1. Navigate to the product page for Emerson 1410S and 781S. 2. Scroll as needed to the green menu bar and click Documents & Drawings. 3. For installation drawings, click Drawings & Schematics and select the appropriate document. 4.
Product Data Sheet 00813-0600-4410, Rev AA April 2020 Emerson Wireless 1410S Gateway with 781S Smart Antenna ■ Gateway connects the WirelessHART® self-organizing networks with any host system ■ Easy configuration and management of self-organizing networks ■ Easy integration into control systems and data applications through serial and Ethernet connections ■ Greater than 99 percent data reliability with industry proven security ■ Ability to leverage sensor data from critical assets to eliminate blind spots
Emerson Wireless 1410S April 2020 Emerson Wireless solution IEC62591(WirelessHART)...the industry standard Self-organizing, adaptive mesh routing ■ No wireless expertise required, network automatically establishes the best communication paths ■ The self-organizing, self-healing network manages multiple communication paths for any given device. If an obstruction is introduced into the network, data will continue to flow because the device already has other established paths.
Emerson Wireless 1410S April 2020 Features and benefits Gain real-time process information with greater than 99 percent wireless data reliability The Emerson Wireless 1410S Gateway with 781S Smart Antenna automatically manages wireless communications in constantly changing environments. With the flexibility of installation, optimal network design and best practices can be easily implemented to achieve maximum data reliability.
Emerson Wireless 1410S April 2020 Emerson Wireless 1410S Gateway ordering information VIEW PRODUCT > Online Product Configurator Many products are configurable online using our Product Configurator. Select the Configure button or visit our website to start. With this tool's built-in logic and continuous validation, you can configure your products more quickly and accurately. Specifications and options See the Specifications and options section for more details on each configuration.
Emerson Wireless 1410S April 2020 Intrinsically safe outputs Code Description A Zone 0 / Div 1: Emerson 781S Smart Antenna may be installed in Zone 0/1/2 & Class I Div 1/2 ★ B Zone 2 / Div 2: Emerson 781S Smart Antenna may be installed in Zone 2 & Class I Div 2 ★ Wireless configuration Code Description A3(1) WirelessHART protocol ★ A6(1)(2) WirelessHART protocol and ISA100 ★ (1) (2) Must order the Emerson 781SA WirelessHART Smart Antenna.
Emerson Wireless 1410S April 2020 Code Description N6 Canada Division 2 Non-Incendive & Zone 2 Type ec ★ N1 ATEX Type ec ★ N7 IECEx Type ec ★ ND ATEX Dust ★ NF IECEx Dust ★ NA No approvals ★ Additional options Conduit adapters Code Description J1 CM 20 Conduit adapters ★ J2 PG 13.5 Conduit adapters ★ J3 ¾ NPT Conduit adapters ★ J5 CM 20, PG 13.
April 2020 Code Description M63 Kuwait, Qatar, Saudi Arabia, UAE I63 Bahrain, Belarus, Israel, Tunisia, Uzbekistan R63 Russian Federation D63 India Q63 Japan F63 Indonesia T63 Taiwan H63 China K63 Korea L63 Malaysia Emerson Wireless 1410S Note By selecting a Cisco spectrum domain, you are selecting an IW6300 Wi-Fi access point and will need to also select an option from the following Cisco option tables.
Emerson Wireless 1410S April 2020 Emerson Wireless 781S Smart Antenna ordering information VIEW PRODUCT > Online Product Configurator Many products are configurable online using our Product Configurator. Select the Configure button or visit our website to start. With this tool's built-in logic and continuous validation, you can configure your products more quickly and accurately. Specifications and options See the Specifications and options section for more details on each configuration.
April 2020 Emerson Wireless 1410S Wireless protocol and operating frequency Code Description A WirelessHART, user configurable transmit rate, 2.4 Hz DSSS, IEC 62951 ★ C ISA100, user configurable transmit rate, 2.
Emerson Wireless 1410S April 2020 Specifications Emerson Wireless 1410S Gateway Functional specifications Power Intrinsically Safe Output Option A: 24 VDC Intrinsically Safe Output Option B: 10.5-30 VDC For best results, use a high quality industrial galvanically isolated power supply. Current draw: Intrinsically Safe Output Option A Operating current draw is based on 7 Watts power consumption.
Emerson Wireless 1410S April 2020 100 wireless devices at 4 seconds 50 wireless devices at 2 seconds 24 wireless devices at 1 second Supported device update rates 1, 2, 4, 8, 16, 32 seconds or 1 to 60 minutes Data reliability Greater than 99 percent Self-organizing IEC 62734 (ISA100) 2.4 to 2.
Emerson Wireless 1410S April 2020 Materials of construction Enclosure housing Engineered polymer Mounting Mounting brackets also permit remote mounting Size Diameter 3.7 in. (9.4 cm) Weight 2.4 lb. (1.1 kg) Enclosure ratings (Emerson 781S) Type 4X and IP66/67 rated Performance specifications EMC performance Meet all industrial environment requirements of EN61326 and NAMUR NE-21. Maximum deviation less than 1% span during EMC disturbance.
00813-0600-4410 Rev. AA April 2020 Global Headquarters Emerson Automation Solutions 6021 Innovation Blvd. Shakopee, MN 55379, USA North America Regional Office Emerson Automation Solutions 8200 Market Blvd. Chanhassen, MN 55317, USA +1 800 999 9307 or +1 952 906 8888 +1 800 999 9307 or +1 952 906 8888 +1 952 204 8889 +1 952 204 8889 RFQ.RMD-RCC@Emerson.com RMT-NA.RCCRFQ@Emerson.
Reference data May 2020 54 Reference Manual 00809-0600-4410 Emerson.
Quick Start Guide 00825-0600-4410, Rev AA March 2020 Emerson Wireless 1410S Gateway
Quick Start Guide March 2020 Safety messages NOTICE This guide provides basic guidelines for the Emerson Wireless 1410S Gateway. It does not provide instructions for diagnostics, maintenance, service, or troubleshooting. Refer to the Emerson Wireless Gateway 1410S Reference Manual for more information and instructions. The manuals and this guide are available electronically on Emerson.com/Rosemount. WARNING Explosion hazard.
March 2020 1 Wireless planning 1.1 Power up sequence Quick Start Guide The Gateway should be installed and functioning properly before power modules are installed in any wireless field devices. Wireless field devices should also be powered up in order of proximity from the Gateway beginning with the closest. This will result in a simpler and faster network installation. 1.
Quick Start Guide 2 PC requirements 2.1 Operating system (optional software only) March 2020 For security setup. Microsoft® supported Windows™ operating systems are acceptable. Some examples are shown below: • Microsoft Windows Server 2019 (Standard Edition), Service Pack 2 • Windows 10 Enterprise, Service Pack 1 2.2 Applications Configuration of the Gateway is done through a secure web interface.
March 2020 3 Quick Start Guide Initial connection and configuration To configure the Gateway, a local connection between a computer and the Gateway needs to be established. Powering the Gateway For the Emerson 1410S, bench top power will be needed to power the Gateway by wiring a 10.5–30 VDC (24 VDC if configured with I.S. barriers) power source. Figure 3-1: Emerson 1410S Gateway Wiring A. B. C. D. E. F. G. H. I. J.
Quick Start Guide 3.1 March 2020 Establishing a connection Connect the PC/laptop to the Ethernet 1 (Primary) receptacle on the Gateway using an Ethernet cable. 3.2 Windows 7 Procedure 1. Click the Internet Access icon on the bottom right of the screen. Figure 3-2: Internet Access 2. Select the Network and Sharing Center. 3. Select Local Area Connection. 6 Emerson.
March 2020 Quick Start Guide Figure 3-3: Local Area Connection 4. Select Properties. 5. Select Internet Protocol Version 4 (TCP/IPv4) then select Properties. Figure 3-4: Internet Protocol Version 4 (TCP/IPv4) Note If the PC/laptop is from another network, record the current IP address and other settings so the PC/laptop can be returned to the original network after the Gateway has been configured. 6. Select the Use the following IP address button.
Quick Start Guide March 2020 Figure 3-5: IP Address 7. In the IP address field, enter 192.168.1.12 (DeltaV Ready enter 10.5.255.12). 8. In the Subnet mask field, enter 255.255.255.0. 9. Select OK for both the Internet Protocol (TCP/IP) Properties window and the Local Area Connection Properties window. 8 Emerson.
March 2020 3.3 Quick Start Guide Windows 10 Figure 3-6: Network Settings Procedure 1. Select the network icon in the lower right corner. 2. Select the Network settings link. 3. Select Change adapter options.
Quick Start Guide March 2020 Figure 3-7: Change Adapter Options 4. Right click the network interface connection that the Gateway is plugged into, and select Properties. 5. Select Internet Protocol Version 4 (TCP/IPv4) then select Properties. 10 Emerson.
March 2020 Quick Start Guide Figure 3-8: Internet Protocol Version 4 (TCP/IPv4) Note If the PC/laptop is from another network, record the current IP address and other settings so the PC/laptop can be returned to the original network after the Gateway has been configured. 6. Select the Use the following IP address button.
Quick Start Guide March 2020 Figure 3-9: IP Address 7. In the IP address field, enter 192.168.1.11 (DeltaV Ready enter 10.5.255.12). 8. In the Subnet mask field, enter 255.255.255.0. 9. Select OK for both the Internet Protocol (TCP/IP) Properties window and the Local Area Connection Properties window. Note Connecting to the Gateway's secondary Ethernet port will require different network settings. Table 3-1: Network Settings 12 Gateway PC/laptop/ tablet Subnet Ethernet 1 192.168.1.10 192.168.1.
March 2020 3.4 Quick Start Guide Disable proxies This procedure may be necessary when using a Chrome browser with Windows operating systems. Procedure 1. Open web browser. 2. Navigate Settings >Advanced. 3. In the System section, click Open proxy settings. Example 3.5 Configure the Gateway To complete initial configuration for the Gateway, follow the steps below. This will have to be done be done for both networks. Procedure 1. Access the default web page for the Gateway at https:// 192.168.1.10.
Quick Start Guide March 2020 Figure 3-10: User Name and Password 2. Navigate to System Settings > Gateway > Ethernet Communication to enter the Network Settings. a) Configure a static IP Address or set for DHCP and enter a Hostname. Figure 3-11: Ethernet Communication b) Restart application at System Settings > Gateway > Backup and Restore > Restart Apps. Note Resetting applications will temporarily disable communications with field devices. 3. Disconnect the power and Ethernet cable from the Gateway.
March 2020 Quick Start Guide 4 Physical installation 4.1 Emerson 1410S2 mounting Find a location where the Gateway has convenient access to the host system network (process control network). 4.1.1 Pipe mount Prerequisites The following hardware and tools are needed to mount the Gateway to a 20in. pipe: • Two 5/16-in. u-bolts (supplied with Gateway • 2-in. mounting pipe • 1/2-in. socket-head wrench Procedure 1.
Quick Start Guide 4.1.2 March 2020 Bracket mount The following hardware and tools are needed to mount the Gateway to a support bracket: Prerequisites • Four 15/16-in. bolts • Mounting support bracket • ⅜-in. drill • ½ -in. socket-head wrench Mount the Gateway using the following procedure: Procedure 1. Drill four 3/8-in. (9,525 mm) holes spaced 3.06-in. (77 mm) apart horizontally and 11.15-in. (283 mm) apart vertically in the support bracket, corresponding with the holes on the Gateway mounting bracket.
March 2020 4.2 Quick Start Guide Connecting the Emerson 1410S with 781S Smart antennas Figure 4-2: Emerson 1410S and 781S Installation A. B. C. D. E. F. G. H. Emerson Wireless 1410S Gateway Terminal connections Shield pair cable Emerson Wireless 781S Smart Antenna Power output RS-485 comm 10.5 to 30 VDC power input Serial modbus Procedure 1. Attach shield pair cable. 2. Tape back shield wire and foils. 4.
Quick Start Guide 4.4 March 2020 Terminating resistors Please reference the Emerson 1410S Gateway and 781S Smart Antenna Reference Manual for configuration of the DIP switches. Three DIP switches are provided to enable termination and biasing resistors to the serial Modbus connection. The switches are found in the electronics housing located above the terminal connections. The three DIP switches are on the right side and the down position in ON. 4.5 Connect to the host system Procedure 1.
March 2020 Quick Start Guide 5 Software installation (optional) 5.1 Installation instructions The 2-disk software pack contains the Security Setup Utility (only required for secure host connections or OPC communications) and AMS Wireless Configurator. The Security Setup Utility is located on Disk 1. Procedure 1. Exit/close all Windows programs, including any running in the background, such as virus scan software. 2. Insert Disk 1 into the CD/DVD drive of the PC. 3.
Quick Start Guide 6 March 2020 Verify operations Operation is verified through the web interface by opening a web browser from any PC on the host system network and entering the Gateway IP address or DHCP host name in the address bar. If the Gateway has been connected and configured properly, the security alert will be displayed followed by the log in screen. Thiswill need to be done for both networks. Figure 6-1: Gateway Log In Screen The Gateway is now ready to be integrated into the host system.
March 2020 7 Quick Start Guide Product certifications Rev: 2.0 7.1 European Directive Information A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EU Declaration of Conformity can be found at Emerson.com. 7.2 Telecommunications compliance All wireless devices require certification to ensure they adhere to regulations regarding the use of the RF spectrum. Nearly every country requires this type of product certification.
Quick Start Guide March 2020 N1 ATEX Increased Safety with Intrinsically Safe Outputs to Zone 2 Certificate SGS20ATEX0057X Markings II 3G Ex ec [ic] IIC T4 Gc (-40°C ≤ Ta ≤ +65°C) Standards EN IEC 60079-0: 2018, EN IEC 60079-7:2015+A1:2018, EN 60079-11: 2012, EN 60079-15:2010, EN 60079-31:2014 N1 ATEX Increased Safety with Intrinsically Safe Outputs to Zone 2 (For use only with the Cisco Outdoor Access Point Model IW-6300H-AC-x-K9) Certificate SGS20ATEX0057X Markings II 3G Ex ec nA [ic] IIC T4 Gc (-40°
March 2020 Quick Start Guide 2. The equipment is not capable of withstanding the 500V electrical strength test as defined in clause 6.1 of EN 60079-7:2015+ A1:2018 and 6.3.13 EN 60079-11:2012. This must be taken into account during installation.
Quick Start Guide March 2020 Standards IEC 60079-0: 2017, IEC 60079-7:2015+A1:2017, IEC 60079-11: 2011, IEC 60079-15:2017, IEC 60079-31:2013 Special Conditions for Safe Use (X): 1. The enclosure’s polyurethane paint finish may constitute an electrostatic hazard. Care should be taken to protect it from external conditions conducive to the build-up of electrostatic charge on such surfaces. The equipment must only be cleaned with a damp cloth. 2.
March 2020 Quick Start Guide NF IECEx Dust-Ignition Proof with Intrinsically Safe Outputs to Zone 0 Certificate IECEx BAS.20. 0022X Markings Ex tc [ia IIC Ga] IIIC T90°C Dc (-40°C ≤ Ta ≤ +65°C) Standards IEC 60079-0: 2017, IEC 60079-7:2015+A1:2017, IEC 60079-11: 2011, IEC 60079-15:2017, IEC 60079-31:2013 Special Conditions for Safe Use (X): 1. The enclosure’s polyurethane paint finish may constitute an electrostatic hazard.
Quick Start Guide 7.5 26 March 2020 Declaration of Conformity Emerson.
March 2020 Quick Start Guide Quick Start Guide 27
Quick Start Guide 28 March 2020 Emerson.
March 2020 8 Quick Start Guide Reference data For information on product specs, dimensional drawings, ordering information or the complete reference manual, see Emerson.com.
*00825-0600-4410* Quick Start Guide 00825-0600-4410, Rev. AA March 2020 Global Headquarters Emerson Automation Solutions 6021 Innovation Blvd. Shakopee, MN 55379, USA North America Regional Office Emerson Automation Solutions 8200 Market Blvd. Chanhassen, MN 55317, USA +1 800 999 9307 or +1 952 906 8888 +1 800 999 9307 or +1 952 906 8888 +1 952 204 8889 +1 952 204 8889 RFQ.RMD-RCC@Emerson.com RMT-NA.RCCRFQ@Emerson.
Quick Start Guide 00825-0700-4410, Rev AA March 2020 Emerson Wireless 781S Smart Antenna
Quick Start Guide March 2020 Safety messages NOTICE This guide provides basic guidelines for the Emerson Wireless 781S Smart Antenna. It does not provide instructions for diagnostics, maintenance, service, or troubleshooting. Refer to the Emerson Wireless 1410S Gateway and 781S Smart Antenna Reference Manual for more information and instructions. The manuals and this guide are available electronically on Emerson.com/Rosemount. This device complies with Part 15 of the FCC Rules.
March 2020 Quick Start Guide Verify operation......................................................................................................................... 11 Product certifications................................................................................................................. 12 Reference data...........................................................................................................................
March 2020 Quick Start Guide 1 Wireless planning 1.1 Power up sequence The Emerson Wireless Smart Antenna and wireless I/O should be installed and functioning properly before the power modules are installed in any wireless field devices. Wireless field devices should also be powered up in order of proximity from the antenna beginning with the closest. This will result in a simpler and faster network installation. 1.
Quick Start Guide 1.3 March 2020 Antenna position The Emerson 781S Smart Antennas should be positioned vertically and approximately 3 ft. (1 m) from large structures, buildings, or conductive surfaces to allow for clear communication to other devices. If installing multiple antennas, it is important that the antennas have three feet of horizontal separation from one another. Figure 1-2: Antenna Position 6 Emerson.
March 2020 2 Intended use 2.1 System architecture Quick Start Guide The Smart Antenna must be used in conjunction with a network manager or network Gateway. The Smart Antenna then functions as a translator between the wired network and a wireless field network.
Quick Start Guide March 2020 3 Physical installation 3.1 Pipe mounting Procedure 1. Insert U-bolt around 2-in. pipe or mast, through the saddle, through the L-shaped bracket, and through the washer plate. 2. Use a 1/2-in. socket-head wrench to fasten the nuts to the U-bolt. 3. Secure the antenna to the L-shaped bracket with a 5/16-in threaded bolt. 4. Use a 5/16-in. wrench to tighten the screw into the housing. Figure 3-1: Mounting 3.
March 2020 Quick Start Guide Figure 3-2: Wiring Guide A. Power B. Data Red - positive Blk - negative Wht - RS-485 comm A Blu - RS-485 comm B Figure 3-3: Emerson Wireless 781S A. Power output B.
Quick Start Guide 4 March 2020 Best practices Twisted shielded pair cable is generally used to wire the serial connection to the Gateway. The Smart Antenna should be installed in a central location of the wireless field network so that it has the most direct connections to wireless devices as possible. 10 Emerson.
March 2020 5 Verify operation 5.1 Emerson 781S Smart Antenna Quick Start Guide The antenna has no exterior lights or LCD displays. Therefore, once it is powered up through the Gateway, its operation must be verified through the Gateway end of the connection. 5.2 Power up sequence The second and third LED’s in the Emerson 1410S correlate to the first and second terminal connections. These lights should be green when the antenna is connected properly. 5.
Quick Start Guide 6 March 2020 Product certifications Rev 1.2 6.1 European Directive Information A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EU Declaration of Conformity can be found at Emerson.com. 6.2 Telecommunications compliance All wireless devices require certification to ensure they adhere to regulations regarding the use of the RF spectrum. Nearly every country requires this type of product certification.
March 2020 6.4 Quick Start Guide Europe I1 ATEX Intrinsic Safety Certificate SGS20ATEX0038X Markings Ex ia IIC T4 Ga (-40°C ≤ Ta ≤ +70°C) Standards EN IEC 60079-0: 2018, EN 60079-11: 2012 Special Conditions for Safe Use (X): 1. The plastic enclosure may constitute a potential electrostatic ignition risk and must not be rubbed or cleaned with a dry cloth 2. The measured capacitance between the equipment enclosure and metallic conduit adapter is 21pF.
Quick Start Guide March 2020 2. The measured capacitance between the equipment enclosure and metallic conduit adapter is 21pF. This must be considered only when the Model 781S is integrated into a system where the process connection is not grounded. I7 IECEx Intrinsic Safety Certificate IECEx BAS 20.0021X Markings Ex ic IIC T4 Gc (–40 °C ≤ Ta ≤ +70 °C) Standards IEC 60079-0: 2017, IEC 60079-11: 2011 Special Conditions for Safe Use (X): 1.
March 2020 6.
Quick Start Guide 16 March 2020 Emerson.
March 2020 Quick Start Guide Quick Start Guide 17
Quick Start Guide 6.7 March 2020 Declaration of Conformity Emerson Wireless 781SC Smart Antenna 18 Emerson.
March 2020 Quick Start Guide Quick Start Guide 19
Quick Start Guide 20 March 2020 Emerson.
March 2020 7 Quick Start Guide Reference data For information on product specs, dimensional drawings, ordering information or the complete reference manual, see Emerson.com.
Quick Start Guide 22 March 2020 Emerson.
March 2020 Quick Start Guide Quick Start Guide 23
*00825-0700-4410* Quick Start Guide 00825-0700-4410, Rev. AA March 2020 Global Headquarters Emerson Automation Solutions 6021 Innovation Blvd. Shakopee, MN 55379, USA North America Regional Office Emerson Automation Solutions 8200 Market Blvd. Chanhassen, MN 55317, USA +1 800 999 9307 or +1 952 906 8888 +1 800 999 9307 or +1 952 906 8888 +1 952 204 8889 +1 952 204 8889 RFQ.RMD-RCC@Emerson.com RMT-NA.RCCRFQ@Emerson.
Reference Manual 00809-0600-4410 Redundant Gateway systems May 2020 B Redundant Gateway systems B.1 Overview Redundancy for the Emerson Wireless 1410S Gateway increases the availability of the wireless field network by providing two sets of physical hardware which operate as a single Gateway system. This section covers setup and installation of a redundant Gateway system. It also covers diagnostics and integration to help monitor the health of the redundant Gateway system.
Redundant Gateway systems May 2020 Reference Manual 00809-0600-4410 The Gateway names will be used in diagnostic messages and host system integration to help identify each Gateway. It is recommended that these names be marked on each physical Gateway, in addition to the configuration settings. Selecting left or right for Gateway A is for visualization purposes only. It has no effect on performance or functionality. Figure B-1: System Settings → Gateway → Redundancy B.3.
Reference Manual 00809-0600-4410 B.3.2 Redundant Gateway systems May 2020 Paired Gateways Once the Gateways have finished the pairing process, Gateway A will appear as the current active Gateway on the left hand side and Gateway B will be the standby Gateway on the right. If significant configuration changes need to be downloaded to the standby Gateway, it may temporarily go offline shortly after the pair process is complete. This is expected behavior and does not represent instability in the system.
Redundant Gateway systems May 2020 Reference Manual 00809-0600-4410 Figure B-3: Pairing Gateways Figure B-4: Paired Gateways B.3.3 Mounting and connections Redundant Gateways follow similar mounting and connection practices as a standalone Gateway. Refer to Mounting the Emerson 1410S2 Gateway for more information. In addition to the standard practices, the following considerations should be taken when installing redundant Gateways. 58 Emerson.
Reference Manual 00809-0600-4410 Redundant Gateway systems May 2020 Mounting The Emerson 1410S Gateway should be mounted in a location that allows convenient access to the process control network as well and provides good coverage for the wireless field network. The two Emerson 781S Smart Antennas should be mounted at the same height and be spaced between 3–9 ft. (1–3 m) horizontally.
Redundant Gateway systems May 2020 Reference Manual 00809-0600-4410 Simplex RS-485 A simplex RS-485 host connection supports Modbus RTU protocol. When using this architecture, connect the secondary Ethernet port on Gateway A directly to the secondary Ethernet port on Gateway B. Then wire the RS-485 ports for both Gateways in parallel to a single serial card at the host system. See Figure D-5, Simplex RS-485 Architecture. Figure B-6: Simplex RS-485 Architecture A. B. C. D. E. F.
Reference Manual 00809-0600-4410 Redundant Gateway systems May 2020 Figure B-7: Dual RS-485 Architecture A. B. C. D. E. F. Engineering station Process control network Controller and I/O Dual serial card RS-485 bus Secondary Ethernet Note By default, only the active Gateway in a redundant system will respond to Modbus polling requests.
Redundant Gateway systems May 2020 Reference Manual 00809-0600-4410 Table B-1: Redundancy Diagnostics Parameter Description Data type REDUNDANT_HEALTHY Overall redundancy status indicating the system Boolean is ready for a switch-over RF_COVERAGE_FAILURE Check to verify that both Gateways have the same RF coverage of the wireless field network REDUNDANT_A_ONLINE Operational status of Gateway A REDUNDANT_A_MASTER Indication if Gateway A is the active system REDUNDANT_A_PING Indication if Gatewa
Reference Manual 00809-0600-4410 Redundant Gateway systems May 2020 Figure B-8: Network Connectivity Check (System Settings → Gateway → Ethernet Communication) B.5 Gateway replacement When replacing or reintroducing a Gateway in a redundant system, always connect both the primary and secondary Ethernet connections before powering the standby Gateway. If the Gateway is being reintroduced (i.e. it was a part of the original redundant system), it will automatically rejoin the redundant system.
Redundant Gateway systems May 2020 64 Reference Manual 00809-0600-4410 Emerson.
Reference Manual 00809-0600-4410 Power specifications May 2020 C Power specifications C.1 Dual mode upgrades The Emerson Wireless 1410S Gateway has the ability to connect two Emerson 781S Smart Antennas. This upgrade can be added upon purchase of the Gateway, or it can be added later through an order option file. This option file can be downloaded through the Gateway web interface.
Power specifications May 2020 C.3 Reference Manual 00809-0600-4410 IEC 62734 Device support Since these devices communicate through a different network, they will appear separate from WirelessHART® devices in the Gateway user interface, but still all at the same IP address and web page. These devices will appear in two separate tables in the Gateway Devices page. Figure C-2: Devices Page On this page, you can see the two device tables for both your WirelessHART devices and legacy ISA100 devices.
Reference Manual 00809-0600-4410 Power specifications May 2020 Figure C-3: Detailed Device Information Page Emerson 1410S/781S 67
00809-0600-4410 Rev. AA 2020 Global Headquarters Emerson Automation Solutions 6021 Innovation Blvd. Shakopee, MN 55379, USA North America Regional Office Emerson Automation Solutions 8200 Market Blvd. Chanhassen, MN 55317, USA +1 800 999 9307 or +1 952 906 8888 +1 800 999 9307 or +1 952 906 8888 +1 952 204 8889 +1 952 204 8889 RFQ.RMD-RCC@Emerson.com RMT-NA.RCCRFQ@Emerson.