Software Manual
Rev 1.3 Series X11CA Computer Annunciators: X11CA Configuration Software User’s Manual
4. X11CA Software Operation
Hardware Control-© 2003 Ronan Engineering 31
? Auxiliary Relay Output Follow
Choose the signal that will trigger the
Auxiliary Relay Output signal from the
X11CA-IM when the switch on the
X11CA-IM is on Run side. The result
depends on the sequence type of each
channel.
Figure 4-19 Auxiliary Relay
Output
Example: The following is the sequence of A-1 type inX11CA-IM
environment.
Signal to Trigger
Auxiliary Relay
Output
Description
No AUX
(No Auxiliary Relay
Output)
Auxiliary Relay output is not available.
FC
(Field Contact)
If the Field Contact input is not normally energized:
§ When the Field Contact goes into an alarm
condition, auxiliary output becomes
energized.
§ When the Field Contact returns to normal
condition, auxiliary output becomes de-
energized.
If the Field Contact input is normally energized
§ When the Field Contact is in an alarm
condition, auxiliary output becomes de-
energized.
§ When the Field Contact returns to normal
condition, auxiliary output becomes
energized.
ACK
(Acknowledge)
If the Field Contact input is not normally energized:
§ When the Field Contact goes into an alarm
condition, the auxiliary output becomes
energized.
§
When
the acknowledge button connected to