Installation manual
Part No 4801-5154 Rev 01-2015 RS-500/600 Series Doors Page 35
NOTE: Refer to the RollSeal SC-325/650 Controller Manual for wiring and initial setup. After wiring the
controller to the door, connect electrical power to the controller. The door is now ready for
operation.
The controller keeps track of the "open" and "closed" positions of the door by means of a mechanical encoder wheel
that is located in the encoder box. The controller electronically counts steps as the wheel turns to keep track of the
door position. The door seals by means of 'hook & loop’ or ‘magnetic’ strips along the edges of the door curtain and
vertical members.
To Operate Door:
1. Depress “Open” switch button mounted on the wall. Door curtain will roll up to 'open' position and find
“HOME” position and drop some to the set upper limit. If door was wired for “timer” it will count down
from set delay and close on its own. If not on wired on “timed” function proceed to step 2 to close.
2. Depress “Close” switch button. Door curtain will roll down to 'closed' position of lower limit and stay
3. Depress button to open or close door as desired.
4. Open and close the door a few times to test door operation and remove any wrinkles in the door curtain.
If you detect any problems, STOP. Disconnect electrical power. Contact your distributor for assistance.
23 Operation of RS-500/600 Series Door with Freezer Kit Included
The controller keeps track of the "open" and "closed" positions of the door by means of a mechanical encoder wheel
that is located in the control box. The controller electronically counts steps as the wheel turns to keep track of the
door position.
The door seals by means floating magnets and laminated steel strips along the edges of the door curtain and vertical
members.
23.1 SC-325 and SC-650 Program Setup for Freezer Mode
For all Freezer Door applications, the SC-325 and SC-650 Controller “P4” program setting must be set to
option “3”. Option “3” will reconfigure the SC-325 and SC-650 Controller “Warning” output for Freezer
Mode. This mode will operate freezer equipment such as blowers or heaters when wired properly (See Wiring
Diagram in the SC-325 and SC-650 Controller manual 4801-5156 Connecting Switches to the SC-325 and
SC-650 Wiring Option -W01). The P4 Door Interlock option 3 “Freezer Mode” is explained in detail below.
P4 - Option 3 = Freezer Mode, No Interlock
When the Freezer Door and SC-325 and SC-650 Smart Controller is used in freezer applications and P4 is set
to 3, the Auxiliary Output Relay is used to operate equipment such as blowers or heaters. *Available on
Software versions V0.21 and later.
Operation of the blowers or heaters will occur ONLY while the door is closed. Closed refers to the
normal operation while the door is below Safety Beam Height.
Auxiliary Output Relay will disengage during door movement, setup operation, jog mode, etc.
Auxiliary Output Relay will engage upon the door stopping below Safety Beam Height.
If the Home Switch is engaged, the Auxiliary Output Relay will turn Off-disengage.
If the door status indicates unknown position, the Auxiliary Output Relay will turn Off-disengage.