Installation manual
26
Technical Specifications
Power Range 700-3000 VA
GENERAL
Rated power 700VA, 1000 VA, 1500 VA, 2000 VA,
3000 VA at p.f 0.7
Technology On-line, double conversion topology with automatic bypass
INPUT
Phase Single phase with ground
Bypass Voltage: 184-265 VAC (user selectable)
Input Voltage range: 120/140/160 VAC-276 VAC
Frequency: 50/60 Hz. Auto selection
Frequency window from mains 45-65 Hz
Synchronization window ± 3Hz.
Input current 700 VA 3A, 1000 VA 4A, 1500 VA 5.7A,
2000 VA 7.7A, 3000 VA 12A
Input Power factor: 0.97
OUTPUT
Output Voltage: 208/220/230/240 VAC, selectable from LCD panel
Voltage regulation: ± 2%
Voltage distortion: < 5% THD at full non-linear load, < 3% THD at full linear load
Frequency regulation ± 0.25 Hz (battery or free running mode)
* 120V at 40% load, 140V at 70%, 160V at 100%.
Dynamic response: ± 9 % max from 100% to 20 % or from 20% to 100 % linear load
Overload capacity: 100-125% 1 min, 125-150% 10 sec
Efficiency: greater than 86%
Power Range 700-3000 VA (19” Rack-mount model)
GENERAL
Rated power 700VA, 1000 VA, 1500 VA, 2000 VA,
3000 VA at p.f 0.7
Technology On-line, double conversion topology with automatic bypass
INPUT
Phase Single phase with ground
Bypass Voltage: 184-265 VAC (user selectable)
Input Voltage range: 120/140/160 VAC-276 VAC
Frequency: 50/60 Hz. Auto selection
Frequency window from mains 45-65 Hz
Synchronization window ± 3Hz.
Input current 700 VA 3A, 1000 VA 4A, 1500 VA 5.7A,
2000 VA 7.7A, 3000 VA 12A
Input Power factor: 0.97
OUTPUT
Output Voltage: 208/220/230/240 VAC, selectable from LCD panel
Voltage regulation: ± 2%
Voltage distortion: < 5% THD at full non-linear load, < 3% THD at full linear load
Frequency regulation ± 0.25 Hz (battery or free running mode)
* 120V at 40% load, 140V at 70%, 160V at 100%.
Dynamic response: ± 9 % max from 100% to 20 % or from 20% to 100 % linear load
Overload capacity: 100-125% 1 min, 125-150% 10 sec
Efficiency: greater than 86%