Installation manual
16
Connection to mains and loads
The following Input and Output cables come supplied with all models
700 VA, 1000 VA, (option)- IEC 320 10 A (Input cable)
1500 VA, 2000 VA Two IEC-IEC 320 10 A (Load cable)
3000 VA (option)-IEC 320 16 A (Input cable)
Two IEC-IEC 320 10 A (Load cable)
l Ensure that the UPS is disconnected from mains and loads while connecting the External Battery
Cabinets, if needed.
l Use the battery cable that comes with the External Battery Cabinet to connect the External Battery
Cabinet to the UPS. Connect a second battery cabinet to the first one with the cable provided if more
than one is to be installed.
l Be aware of UPS parameters and changing the Battery pack quantity when using the external battery
cabinets (see chapter 7.2)
l Connect the Input cable to the UPS and connect the other end to a grounded outlet. The batteries will
automatically charge when connected to the mains. Please realize that although you may start using the
UPS immediately, maximum back-up time will still not be available, so it is recommended to charge
the batteries for a minimum of 8 hours before use.
l If unit instantly shows a “Site Wiring Fault”, rotate the connector (Schuko) (see chapter 7.4).
l After charging, connect the loads to the UPS (see the example in fig 3).
l Do not connect any devices that have the possibility of overloading the UPS or drawing half-wave
rectified current, such as hair dryers or vacuum cleaners.
l Should computer or alarm connections be used, use connections according to chapter 6 of the manual
provided with that option. The connections can be referred to on the rear panel.
l The installation is now complete