User Manual
Remote Control
R&S
®
NGE100B
86User Manual 5601.1343.02 ─ 04
[SOURce:]VOLTage:PROTection:TRIPped?
This command queries the OVP tripped status of the previous selected channel.
Return values:
<arg0> ON | OFF
ON
OVP is tripped
OFF
OVP is not tripped
Example:
INST OUT1
VOLT:PROT:TRIP? -> OFF
OVP of Ch 1 has not tripped.
Usage: Query only
[SOURce:]VOLTage:PROTection[:STATe] <arg0>
This command defines or queries the OVP state for the previous selected channel.
Parameters:
<arg0> 1 | 0
1
OVP is activated.
0
OVP is deactivated.
Example:
INST OUT1
VOLT:PROT ON
OVP of Ch 1 is activated.
VOLT:PROT? -> 1
Return the OVP state of the selected channel.
[SOURce:]VOLTage:PROTection:LEVel <Voltage>
This command defines or queries the OVP value of the previous selected channel.
Parameters:
<Voltage> {<Voltage> | MIN | MAX}
<Voltage>
Set the OVP value in the range of 0 mV up to 32.2 V (adjustable
in 100 mV steps)
MIN
Set the OVP value to minimum.
MAX
Set the OVP value to maximum.
Default unit: V
Remote Control - Commands