Specifications

12 ROCPOWER SMARTOWERusermanual
CHAPTER4
OperationTest
TurnOfftheUPS
PushtheOFFSwitchforatleastthree(3)secondstoturnOFFtheUPS.IfyoupresstheOFF
switchlessthanthree(3)seconds,theUPSwillnotexecutetheshutdowncommand.Incaseof
overload,outputshortcircuitsorwhenthebatterycutoffpointisreachedintheBackupMode,
theUPSwillbeepforfive(5)secondsandthenautomaticallyshutitselfdown.
PluginCharge
IftheInputPowerCordiscorrectlyconnectedtothewalloutletandtheutilityisnormal,the
UPSwillchargeautomaticallywithoutturningontheUPS.Youhavetochargeforatleasteight
(8)hourseverythree(3)monthstoavoid
batterydischargewhentheUPSisinanidle condition.
AutoRestart
TheUPSwillautomaticallyrestarttoprovideenergytotheoutputiftheutilityrecoverswithin
24hoursafterbatterycutoff.TheBackupLEDwillflasheveryfive(5)secondsduringcutoff.The
UPSwillnotautorestartif
theutilitydoesn’trecoverwithin24hours.TheUPSmustbe
manuallystartediftheutilityfailstorecoverwithin24hours.TheUPSautorestartcanbe
canceledbypressingOFFswitchforthree(3)seconds.
AlarmSilence
TheAlarmmaybeturnedOFFbypushingtheONSwitchforapproximatelyone(1)secondin
theBackupMode.TheAlarmremainssilentunlessawarningorfaultconditionoccurs.
Test
UnderUtilityNormalcondition,pushtheONswitchforthree(3)secondstoexecutethe
BatterySelftestfunction.Whenthebatteryisnormal,itwillenterintoBatteryBackupMode
for10SecondsthenreturnbacktoUtilityMode.Ifthebattery’svoltageislow,theBattery
ReplacementLEDwillblinkforfive(5)secondsthenextinguishtostoptheselftestprocedure.
Ifthebatteryisweakordead,theBatteryReplacementLEDwillsteadilyilluminate.