Specifications
ROCPOWER
–
MAGNUSandROCFORCE‐ ParallelSystemInstallationGuide 9
BatteryInput
RecommendedCircuitBreakerinstalledintheinput/outputoftheUPSshallbetype“C”or“D”
andtheircurrentratingsshallbeaslisted.
Start‐upOperationProcedure
PuttheUPSinanappropriatelocationasspecifiedinabove.
Themaximumlengthofthecommunicationconnectingwiresshallbelessthan7metersor23
feetanditshouldbeconnectedasa“Ring” loopasindicatedinFig.5.
Model Maximum
Current
Conductor
Section
4.5KVA,6KVA
8KVA&10KVA
25A
40A
AWG#10
AWG
#
10
Model Input Output
4.5KVA,6KVA
8KVA&10KVA
40A
60A
30A
50A
INPUT
OUTPUT
CONTROL CONTROL CONTROL
CONTROL
I
O
I
O
I
O
I
O
1050mmRJ‐45communication
1900mmRJ‐45communicationconnecting
Max.25M;allInputPowercablesshallbethesame
Max.25M,allOutputPowercablesshallbethesame
Fig.5