Specifications

ROCPOWER
MAGNUSandROCFORCE‐ ParallelSystemInstallationGuide 9
BatteryInput

RecommendedCircuitBreakerinstalledintheinput/outputoftheUPSshallbetype“C”or“D”
andtheircurrentratingsshallbeaslisted.

StartupOperationProcedure
PuttheUPSinanappropriatelocationasspecifiedinabove.
Themaximumlengthofthecommunicationconnectingwiresshallbelessthan7metersor23
feetanditshouldbeconnectedasa“RingloopasindicatedinFig.5.
Model Maximum
Current
Conductor
Section
4.5KVA,6KVA
8KVA&10KVA
25A
40A
AWG10
AWG
10
Model Input Output
4.5KVA,6KVA
8KVA&10KVA
40A
60A
30A
50A
INPUT
OUTPUT
CONTROL CONTROL CONTROL
CONTROL
I
O
I
O
I
O
I
O
1050mmRJ45communication
1900mmRJ45communicationconnecting
Max.25M;allInputPowercablesshallbethesame
Max.25M,allOutputPowercablesshallbethesame
Fig.5