InstallationInstructions
Ensuretoseparatelyinstallthepowerwiresandcablesusedfortheinput,outputandbattery
connections.Thewiresandcablesshouldnottouchasthiswillcauseunnecessarynoise
interference
Thecommunicationwiresforparallelfunctionandotherwiresforcontrolsignals,includingRJ45,
RS232,RS485,USB,EPOandShutdowncablesshallbekeptawayfromthosewiresandcables
mentionedintheabove paragraph(powerwiresandcables).Ifitisnotpossibletodoso,please
putthemat
90degreeorleast20cmdistancefromeachotherasindicatedinFig.4.
EnsurethattheUPSisproperlygroundedandtheleakagebreakerinstalledbeforetheUPSis
connectedtotheACpowerlineoranoutputdeviceisconnectedtotheUPS.
Pleaserefertothespecsofinputcurrent,outputcurrentandrecommendedconductorslisted
asbelow:
ACinputandoutput
Model Maximum
Current
Conductor
Section
4.5KVA,6KVA
8KVA&10KVA
33A
50A
AWG#9
AWG
#
9
Incorrect Correct
A
B
90°
20cm
B
A
B
A
AÆCommunicationorControlsignalwires
BÆPowerwires&cables
Fig.4