Instruction manual

ROC/FloBoss Accessories Instruction Manual
6-29 Sensor / Transducer Accessories Rev. Feb/05
Figure 6-14. Analog Input – Scanning Enabled
4. Reset the DVS to factory defaults, using the following procedure.
To reset the FloBoss 503 DVS configuration back to the original factory defaults:
1. Launch ROCLINK software.
2. Select Configure > I/O > AI Points.
3. Select Analog Inputs 1 (Point Number A1).
4. Select the Advanced tab.
5. Enter 32767 in the Adjusted A/D 100% field. Refer to Figure 6-15.
Figure 6-15. Analog Input – Advanced
6. Click Apply.