Specifications

ROCPOWER
ROCFORCE‐ ParallelRedundancyOnLine‐usermanual 28
DrawingV1,V2,V3andV4showtheoperationmodesoftheUPS.TheyareOnline,Eco
(Economic)Mode,fixed50HzOutputorfixed60HzOutput.
DrawingWshowstheadjustmentsoftheInverterOutput.Itmaybesetat0%,+1%,‐1%,+2%,
2%,+3%,or‐3%.
Drawing
XshowsaspecifiedaddressandpositionoftheUPSwhentheUPSisinParallelMode.
Thesettablenumbersarefrom1stto4th.
DrawingYshowsparallelfunctionstatus.Thenumber“01”means“Disable,”and“02”means
“Enable.”
Whenthesettingchangesarecompleted,pressthe
downkeyseveraltimestoturnthe
LCDscreendisplaytodrawingZ,thenpresstheenter
keytosavechanges.TheLCDscreen
willshowdrawingAA,promptingUPStobereset.Thechangesmaybeabortedbeforesaving
bypressingtheOFF
keyfor5secondsanytimeunderSettingMode.TheLCDscreenwill
returntoDrawingAA,whichmeansyoursettingchangeswerenotsaved.
Z
*PleasepressEnterkeytosavedata.
AA
*ItshowstheUPSneedstobereset.
TurnOFFthe
UtilityInputbreaker.
YourSettingchangesarecomplete.
Troubleshooting:WhentheUPSisintheOFFpositionduetoanabnormalcondition.
Ifanabnormalconditionoccurs,theUPSwilllockitselfinOFFpositionasshownin
drawingAAandanabnormalmessagewillshowintheLCDscreen.
