Specifications
ROCPOWER
–
ROCFORCE‐ ParallelRedundancyOn‐Line‐usermanual 27
*ItshowsOutputVoltageAdjustment%from0%to3%or‐0%to‐3%.
X
*ItshowsUPSIdentificationNumberis“01.”
Y
*ItshowstheUPSparallelfunctionisdisabled.
Pressthescrollup
keypadusespecialfunctions.TheFunctionsincludesbuzzerON
(drawingQ1),buzzerOFF(drawingQ2,alarmissilentforanyUPSWarnings)andSelf‐Test
OFF(drawingR1)orSelf‐TestON(drawingR2.UPSwillexecutebatterytestfor10seconds.
IftheSelf‐Testis
successful,itwillshowasDrawingE1,otherwise,itwillshowasdrawingE2
withanerrormessageatthesametime.)
UPSDefaultSettingsandtheiralternatives
BeginwiththeUPSOFF.PresstheONSwitch
andscrolldown keypadssimultaneously
forapproximatelythree(3)seconds.ThebuzzerwillsoundtwiceandtheLCDdisplayscreen
willdisplaydrawingQ1.TheUPSisnowinSettingMode.
Refertopage23‐Q2toscrolldowntheLCDscreen.
Theremainingdefaultsettingsmaybechangedbypressing
thescrollup key,exceptthe
Buzzer(drawingQ1&Q2)andtheSelf‐Test(drawingsR1&R2).
DrawingsS1andS2showthebypassinputrangeof184VAC~260VACor195VAC~260VAC.
DrawingTshowsthebypassfrequencyrangeoftheInverterOutput.Theacceptablesetting
valuesare±3Hzand±1Hz.
Drawing
UshowstheacceptableInverterOutputVoltage.Thevoltageis200VAC,208VAC,
220VAC,230VAC,or240VAC.