Publication 1783-UM002C-EN-P - April 2009 45
Chapter 2
4. Use a flat-head screwdriver to torque the power and relay connector
captive screw (above the installed wire leads) to 0.23 N•m (2.0 lb•in.).
5. Repeat steps 1...4 to insert the input and output wires of an additional
external alarm device into the second power and relay connector.
The following figure shows the completed wiring for two power
supplies and two external alarm devices.
1 External device, relay wire A connection 1 2 External device, relay wire A connection 2
-
24
!
6
!
1
2
VRTA A
31785-M
V
RT