Hardware Reference, Installation and Troubleshooting Owner manual

Install and Wire the Drive
2-5
Power connections
Motor
1D, 1C
Bus bars 50 x 10,
Hole 13.5 mm
AC-Line
1U, 1V, 1W
Bus bars 40 x 10,
Hole 13.5 mm
Protection
earth PE
Bolt M12
Torque 15 Nm
Weight: 83 kg
Cooling air: 814 m
3
/h
Air flow direction: from bottom to top
Minimum clearances
for air circulation: 100 mm
Figure 2.4: Mounting Data for 800 A Drives.