Configuring Other Parameters
13-1
C
HAPTER
13
Configuring Other Parameters
The parameters listed in this section may or may not apply to your application. Refer to
the WebPak 3000 software manual (D2-3444) for more information about each of
these parameters.
13.1 Analog Outputs
The Regulator board provides two analog outputs that are unfiltered or filtered. The
I/O Expansion board has two unfiltered analog outputs,
ANLG
OUT
3 and 4. One can
generate a bipolar DC voltage only. The other can be configured to generate a DC
voltage from a 0 to +/-10 VDC, 4 to 20 mA, or 10 to 50 mA signal.
These outputs can be scaled to generate DC voltage signals as low as 5 V, but
maximum resolution (0.025%) is obtained when the full scale output signal is used.
The full scale value (FSV) is determined based on the selected parameter group: load,
speed, voltage, power, field, or other.
Analog outputs are read every 10 ms.
Use This Chapter for These Applications:
Constant Diameter Speed Regulator
Variable Diameter Speed Regulator
Constant Diameter Current Regulator
Variable Diameter Current Regulator
Constant Diameter Position Regulator
Variable Diameter Position Regulator
Constant Diameter Tension Regulator
Variable Diameter Tension Regulator
Generic