WebPak 3000 DC Drive Application Workbook, Version 1.1
3.1 The Speed Loop Reference
Refer to figure A.4 in Appendix A of the software manual (D2-3444) as you set up the
speed loop reference.
The setup of the speed reference depends on the control source selected. The control
source selections are:
KEYPAD
- The drive uses the reference from the OIM.
Important:
If you select
KEYPAD
as the control source, the drive can be used to
regulate speed only.
TERMBLK
- The drive uses the reference from the Regulator board terminal strip.
SERIAL
- The drive uses the reference from a serial device (for example, a PC running
WebPakCS software).
NETWORK
- The drive uses the reference from the network.
þ
To select the control source:
If you are using the WebPakCS software to program the drive, you configured
the control source during the initialization process by setting
CONTROL
SOURCE
SELECT
(P.000).
If you are using the OIM to program the drive, select the control source
using
If the
CONTROL
SOURCE
(P.000) =
TERMBLK
:
Specify the line speed signal type in
LINE
SPEED
REF
SELECT
(P.103). The
choices are:
ANALOG
FREQUENCY
IN
- The frequency input is typically used to daisy-chain
multiple drives.
If
LINE
SPEED
REF
SELECT
(P.103) =
ANALOG
:
Verify that an analog line speed reference is connected to
terminals 19(+) and 20(-) on the Regulator board.
Set
LINE
SPEED
SIG
TYPE
(P.100).
Important:
Jumpers J10 and J12 must be set for the type of line speed signal
selected. See the drive hardware manual (D2-3443) for instructions.
Set
LINE
SPEED
GAIN
ADJ
(P.101) to adjust the gain for the line
speed input.
Range:
KEYPAD
,
TERMBLK
,
SERIAL
,
NETWORK
P.000
=
Range:
ANALOG
,
FREQUENCY
IN
P.103 =
Range: 0 to 10V, +/-10V, 4 to 20mA, 10 to 50mA
P.100 =
Range: 0.750 to 2.250
P.101 =