2
Using WebPak 3000 ControlNet Communications Option Board I/O With a ControlLogix Processor
You can also contact the Rockwell Automation technical support division for the product related to your
question:
Required Equipment and Software Versions
Table 2 lists the equipment and software versions required to set up communications between a ControlLogix
processor and a WebPak 3000 drive.
If the firmware in your ControlLogix equipment does not meet the above requirements, contact the Control and
Information Group technical support division (1-440-646-6800) to obtain a copy of the appropriate
ControlFlash upgrade kit.
Configuring an I/O Connection
Before configuring an I/O connection, you must:
Configure the WebPak 3000 drive network parameters (refer to chapter 3 in D2-3425-2), set the network
drop number appropriately, and set the control source to network.
Verify that you have used RSNetWorx for ControlNet to configure the network containing the ControlLogix
chassis and WebPak 3000 drive.
Use the following procedure to configure an I/O connection:
Step 1. After opening the RSLogix 5000 software, verify that you are off-line with the ControlLogix processor.
You can configure an I/O connection when starting a new project or after opening an existing project,
but I/O can only be configured off-line.
Division Telephone E-mail/Web Address
Rockwell Software
(RSLinx, RSNetWorx for ControlNet,
RSLogix 5000 software)
1-440-646-7800 http://www.software.rockwell.com/support/
Control and Information Group
(ControlLogix system, ControlNet
network)
1-440-646-6800 RACleAskTheExpert@ra.rockwell.com
Table 2 Required Equipment and Software Versions
Equipment Description Part Number Version
RSLinx software 9355-WABENE Version 2.20 or later
RSNetWorx for ControlNet software 9357-CNETL3 Version 2.25 or later
RSLogix 5000 software 9324-RDL300ENE Version 6.00 or later
ControlLogix processor 1756-L1 Firmware version 6.20
or later
ControlLogix ControlNet bridge (1756-CNB or
1756-CNBR)
1756-CNB or 1756-CNBR
Series A, V1.19
Series B, V2.27 or later
Series D, V5.22
FlexPak 3000/WebPak 3000 ControlNet Network
Communications board
915FK2101 Version 2.2 or later