Manual
2-4
VSM500 DeviceNet Option Board
Step 3. On the DeviceNet option board, set switches 6 through 1 to a unique
DeviceNet address between 0 and 63. The default switch setting is 63.
Step 4. On the DeviceNet option board, set switches 7 and 8 to select the data rate
at which the network is operating. The default switch setting is to use the
setting of parameter 104 [
NV BAUD RATE].
Table 2.2 – DeviceNet Option Board Switch Settings (Switches 1-6)
Node
Address
1
Switch
6 ----> 1
Node
Address
1
Switch
6 ----> 1
Node
Address
1
Switch
6 ----> 1
Node
Address
1
Switch
6 ----> 1
0 000000 16 010000 32 100000 48 110000
1 000001 17 010001 33 100001 49 110001
2 000010 18 010010 34 100010 50 110010
3 000011 19 010011 35 100011 51 110011
4 000100 20 010100 36 100100 52 110100
5 000101 21 010101 37 100101 53 110101
6 000110 22 010110 38 100110 54 110110
7 000111 23 010111 39 100111 55 110111
8 001000 24 011000 40 101000 56 111000
9 001001 25 011001 41 101001 57 111001
10 001010 26 011010 42 101010 58 111010
11 001011 27 011011 43 101011 59 111011
12 001100 28 011100 44 101100 60 111100
13 001101 29 011101 45 101101 61 111101
14 001110 30 011110 46 101110 62 111110
15 001111 31 011111 47 101111 63 111111
1
If switches 7 and 8 are both On (1), then the DeviceNet option board uses the node address from parameter 103 [NV MAC ID]. The default
parameter setting is 63.
Table 2.3 – DeviceNet Option Board Switch Settings (Switches 7-8)
Data Rate Switch 8 Switch 7
125 kBPS 0 0
250 kBPS 0 1
500 kBPS 1 0
Set by parameter 104 [
NV BAUD RATE]
1
1
The default parameter setting is autobaud.
11