Instruction Manual

Publication D2-3449-1 March 2000 2000 Rockwell International Corporation. All rights reserved. Printed in USA.
1999 Rockwell Automation Corporation. All Rights Reserved
Reach us now at www.rockwellautomation.com
Wherever you need us, Rockwell Automation brings together leading
brands in industrial automation including Allen-Bradley controls,
Reliance Electric power transmission products, Dodge mechanical power
transmission components, and Rockwell Software. Rockwell Automation’s
unique, flexible approach to helping customers achieve a competitive
advantage is supported by thousands of authorized partners, distributors
and system integrators around the world.
Americas Headquarters, 1201 South Second Street, Milwaukee, WI 53204, USA, Tel: (1) 414 382-2000, Fax: (1) 414 382 4444
European Headquarters SA/NV, avenue Herrmann Debroux, 46, 1160 Brussels, Belgium, Tel: (32) 2 663 06 00, Fax: (32) 2 663 06 40
Asia Pacific Headquarters, 27/F Citicorp Centre, 18 Whitfield Road, Causeway Bay, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846
Reliance Electric Standard Drives Business, 24800 Tungsten Road, Cleveland, OH 44117, USA, Tel: (1) 888 374 8370, Fax: (216) 266 7095
Publication D2-3464 - March 2000
2000 Rockwell International Corporation. All rights reserved. Printed in USA.
VSM500 Integrated Drive/Motor CE Filter Option Specifications
VSM-CE-1I VSM-CE-3I VSM-CE-1E VSM-CE-3E
Input Voltage 115/230 VAC 230/460 VAC 115/230 VAC 230/460 VAC
Input Phases Single Phase Three Phase Single Phase Three Phase
Frequency 50/60 Hz
Rated Current 14 amps 9 amps 14 amps 9 amps
Power Dissipation 5 watts
Leakage Current (Worst Case) 0.5 mA
Weight 0.33 Kg
(0.73 lb)
0.45 Kg
(0.99 lb)
4.72 Kg
(10.41 lb)
4.89 Kg
(10.78 lb)
Enclosure Internal NEMA 12/IP 65
Operating Temperature 0° to 40°C (32° to 104°F)
Storage Temperature -40° to 85°C (-40° to 185°F)
Relative Humidity 5% to 95%, non-condensing
Vibration 1 G operational, 2.5 G non-operational
Shock 15 G operational, 30 G non-operational
Altitude 1000 meters (3300 feet) without derating. For every 91.4 meters (300 feet)
above 1000 meters, derate current by 1%. Above 3000 meters (10,000 feet),
consult your Reliance Electric Sales Office.
International Standards and
Approvals
U
L
®
L
I
S
T
E
D
9
6
6
X
I
N
D
C
O
N
T
E
Q
UL508C
U
L
®
L
I
S
T
E
D
9
6
6
X
I
N
D
C
O
N
T
E
Q
C
CSA 22.2
EMC Directive 89/336
LV: EN 50178, EN 60204
EMC: EN 61800-3, EN 50081-1, EN 50082-2