Owner manual

Setting the Drive Jumpers
2-3
2.4 Setting the V/Hz Curve Jumpers (J9 through J12)
Jumpers J9 through J12 set the frequency break point for the V/Hz Curve . The
breakpoint is the frequency at which the output voltage reaches the maximum voltage.
Below this point the output voltage and frequency increase together. This feature is
required to allow the drive to work with motors rated at various frequencies. Figure 2.2
shows a general V/Hz curve.
Figure 2.2 – V/Hz Curve
Table 2.2 – V/Hz Curve Jumper Settings
Jumpers
Frequency at Maximum VoltsJ9 J10 J11 J12
1 1 1 1 42 Hz
0111 46 Hz
1 0 1 1 50 Hz
0011 53 Hz
1 1 0 1 56 Hz
0101 60 Hz
1 0 0 1 63 Hz
0001 66 Hz
1 1 1 0 70 Hz
0110 74 Hz
1 0 1 0 77 Hz
0010 81 Hz
1 1 0 0 85 Hz
0100 88 Hz
1 0 0 0 92 Hz
0000 95 Hz
Boost
F (Hz)
V
V
max