Statistics Mode Control Variable Value Result
Max Scan Rate
False
True (Boolean)
0
non-zero (Integer)
Max value will remain until next cycle
completed.
Max value then updated with time of next
complete cycle.
True False (Boolean)
non-zero
0 (Integer)
Triggers a reset
Scan Rate
False
True (Boolean)
0
non-zero (Integer)
No effect (data updated every cycle)
True False (Boolean)
non-zero
0 (Integer)
No effect (data updated every cycle)
Average
False
True (Boolean)
0
non-zero (Integer)
Average value will remain until next cycle
completed.
Average value then updated with time of
next complete cycle.
True False (Boolean)
non-zero
0 (Integer)
Triggers a reset
Table 13 Modbus Statistics Control
The slave poll scan is defined as the time taken to poll a slave for all messages in the poll list. The first
message defined in the poll list is taken as the start and end point of the timing sequence. This is
illustrated in the diagram Figure 14 below.
Sequence No. Message
1 Slave 1 Msg 1
2 Slave 2 Msg 1
3 Slave 3 Msg 1
4 Slave 1 Msg 2
5 Slave 2 Msg 2
6 Slave 3 Msg 2
7 Slave 1 Msg 3
8 Slave 2 Msg 1
9 Slave 3 Msg 3
10 Slave 1 Msg 4
11 Slave 2 Msg 2
12 Slave 3 Msg 1
13 Slave 1 Msg 1
14 Slave 2 Msg 1
15 Slave 3 Msg 2
Figure 14 Slave Poll timing
Slave 1
Tstart
Slave 1
Tstop
Slave 3
Tstop
Slave 2
Tstop
Slave 2
Tstart
Slave 3
Tstart