User guide
Trusted
TM
RTD FTA T8841
Issue 6 Nov 07 PD-T8841 12
5. Link Assignments
The functions of the links are detailed below.
5.1. Two Wire Operation
The links listed in the table below must be fitted for 2-wire operation. The RTD FTA defaults to 3-wire
operation if the links detailed are not fitted.
Channel Link
1 LK93
2 LK89
3 LK94
4 LK90
5 LK95
6 LK91
7 LK96
8 LK92
Table 4 Two Wire Link Assignments
5.2. Voltage Output
The links listed in the table below must be fitted for voltage output. The RTD FTA defaults to current
output operation if the links detailed are not fitted.
Channel Link
1 LK1
2 LK45
3 LK2
4 LK46
5 LK3
6 LK47
7 LK4
8 LK48
Table 5 Voltage Output Link Assignments