User guide

Trusted
TM
Module T8442
Issue 8 Apr 10 PD-T8442 55
The Trip output channels also report their status as one of eight pre-defined states.
Table 20 shows the default relationship between the Trip output operational state and its associated
indicator state.
Output State Description Indicator State
0 State invalid Off
1 No Coil Vfield Off
2 Coil de-energized Off
3 Coil not connected Green - flashing
4 Coil energized Green
5 Not used Red
6 Field fault Red
7 State faulted or unknown Red - flashing
Table 20 Default Relay Output Status Indication
Note: Although the Input and Output states are pre-defined, the system configuration utility allows the
user to individually associate Indicator states to both Input and Output states. This allows the
user to create custom indication schemes for their application. This can be achieved by
implementing the procedure for configuring the SYSTEM.INI file detailed in PD-8082B.