User guide

Trusted
TM
Module T8442
Issue 8 Apr 10 PD-T8442 22
Pin Signal Name Description
C1 SMART_C Smart Slot Link C
C2 - Not used
C3 PASSIVE_PULSE_POS_G1_1 Group 1, Channel 1, Positive Passive Speed input
C4 PASSIVE_PULSE_NEG_G1_1 Group 1, Channel 1, Negative Passive Speed input
C5 PASSIVE_PULSE_MID_G1_1 Group 1, Channel 1, Passive Speed input Bias
C6 VFIELD_P15_G1_1 Group 1, +15V sensor power supply output 1.
C7 VFIELD_M15_G1_1 Group 1, -15V sensor power supply output 1.
C8 VFIELD_P15_G1_2 Group 1, +15V sensor power supply output 2.
C9 VFIELD_M15_G1_2 Group 1, -15V sensor power supply output 2.
C10 VF_24V_G1_1 Group 1, +24V field power supply input 1.
C11 VF_24V_G1_2 Group 1, +24V field power supply input 2.
C12 VF_RTN_G1 Group 1, field power supply return.
C13 PASSIVE_PULSE_POS_G2_1 Group 2, Channel 1, Positive Passive Speed input
C14 PASSIVE_PULSE_NEG_G2_1 Group 2, Channel 1, Negative Passive Speed input
C15 PASSIVE_PULSE_MID_G2_1 Group 2, Channel 1, Passive Speed input Bias
C16 VFIELD_P15_G2_1 Group 2, +15V sensor power supply output 1.
C17 VFIELD_M15_G2_1 Group 2, -15V sensor power supply output 1.
C18 VFIELD_P15_G2_2 Group 2, +15V sensor power supply output 2.
C19 VFIELD_M15_G2_2 Group 2, -15V sensor power supply output 2.
C20 VF_24V_G2_1 Group 2, +24V field power supply input 1.
C21 VF_24V_G2_2 Group 2, +24V field power supply input 2.
C22 VF_RTN_G2 Group 2, field power supply return.
C23 PASSIVE_PULSE_POS_G3_1 Group 3, Channel 1, Positive Passive Speed input
C24 PASSIVE_PULSE_NEG_G3_1 Group 3, Channel 1, Negative Passive Speed input
C25 PASSIVE_PULSE_MID_G3_1 Group 3, Channel 1, Passive Speed input Bias
C26 VFIELD_P15_G3_1 Group 3, +15V sensor power supply output 1.
C27 VFIELD_M15_G3_1 Group 3, -15V sensor power supply output 1.
C28 VFIELD_P15_G3_2 Group 3, +15V sensor power supply output 2.
C29 VFIELD_M15_G3_2 Group 3, -15V sensor power supply output 2.
C30 VF_24V_G3_1 Group 3, +24V field power supply input 1.
C31 VF_24V_G3_2 Group 3, +24V field power supply input 2.
C32 VF_RTN_G3 Group 3, field power supply return.
Table 4 Field Interface Connector Pin Assignment (Column C)