1.3.6. Speed Monitor Module Safety Features
The T8442 system is able to provide uninterrupted functionality, speed monitoring and output control
functions under the following circumstances:
Complete failure of Trusted
T
M
system processors.
Complete failure of any or all communication links between the T8442 and the Trusted
TM
system processors.
The following safety strategies are also observed:
T8442 operating parameters are downloaded from the Trusted
TM
system processors on
system or module initialisation (start-up).
It is not possible to change the safety parameters for a speed input group while any input in
that group is above zero speed.
Over-speed and over-acceleration shutdown parameters are downloaded from the Trusted
T
M
system processors on module initialisation.
It is not possible to increase the over-speed or over-acceleration thresholds beyond the safety
limits passed at initialisation. These parameters may be moved in a safe direction via the
IEC1131 TOOLSET.
A standby T8442 module is educated with operating parameters from the active T8442 module
prior to on-line replacement using the Trusted
TM
system companion slot method. The
Trusted(TM) Smart Slot method of on-line replacement is not supported by this module.
Over-speed test mode is limited by a configurable timer.
Every group-specific configuration parameter can be changed when the group is at zero
speed.
The safety case for the module is maintained within the module while the turbine is running
and cannot be affected by the Trusted
TM
system processor in any way.