Instruction Manual

Trusted
TM
Power System T823X
Issue 9 Dec 08 PD-T823X 21
4.6. Environmental Characteristics
Parameter Min Typ Max Unit Note
Storage Temperature -40 -85 °C
Operating
Temperature (note 1)
0 - 60 °C 1. Derate at 1.333%/°C, 45°C to 50°C 2.
Derate at 4.667%/°C, 50°C to 60°C
Acoustics 47 52 dBa Sound Pressure Level at 1m
Humidity (non-
condensing)
5 95 %
Altitude -60 3962 m Derated at 2°C/304m above 2438m.
Electro Static
Discharge
IEC1000-4-2 Level 3 stand-alone
Electromagnetic
Immunity (error free)
IEC1000-4-3 Level 2 stand-alone
Isolation Voltage 3,000
1,500
1,500
VAC
VAC
VAC
Primary to Secondary
Primary to chassis GND,
Secondary to chassis GND
MTBF 4 x 10
5
hours @110Vinput 80% load, T
A
= 30
o
C
Vibration Meet IEC68-2-6
Shock Meet IEC68-2-36
Weight 2.3 kg
Table 6 Environmental Characteristics
Figure 9 Operation Derating Curve