Instruction Manual

Trusted
TM
Power System T823X
Issue 9 Dec 08 PD-T823X 18
4.2. Input Specification
Parameter
Min Typ Max Unit Condition
Input voltage 90 264 Vac
Input Frequency 47 63 Hz
Inrush Current (peak) per pack
50
<25
A
A
Full load
No load
Input current 0.2 A No load
Power Factor 0.95 0.99 > 50% of full load
Input Leakage Current 1.7 mA 264Vac, 50Hz
Lighting Surge & Transients
(damage free operation)
IEC1000-4-5 Level 3
IEC1000-4-4 Level 3
Hold Up Time 20 mS At 600W
EMC (conducted) CISPR22 Class B,
EN55022 Class B, with 3dB
margin
Table 3 Input Specification
4.3. Line Harmonics
Active power-factor correction circuitry ensures that this Power Pack meets the requirements of
IEC1000-3-2.