Assembly User Manual

I/O Power Supply Assembly
(T8060,T8062)
PD
-
6050
Mar
-
06
15
Specifications (Continued)
Operating Humidity
0 to 95% relative humidity, non
-
condensing
Vibration
10 to 55 Hz:
±0.15mm
Shock
Operating:
15 g, ½ sine wave, 11 msec
Electromagnetic Interference
IEC 801 Part 2
-
Electrostatic
Discharges
IEC 801
Part 3
-
Radiated
Electromagnetic Fields
IEC 801 Part 4
-
Transients
and Bursts
IEC 801 Part 5
-
Surge
Immunity
ANSI/IEEE C37.90
-
Surge
Withstand Capability
Level 3: Contact discharge of
6 kV
Level 3: 10 V/M, 27 MHz
-
500 MHz
Level 4: 2 kV, 2.5 kHz for
t
= 60 sec
Level 3: 2 kV
2.5 kV damped 1 MHz sine
wave
4 kV bi
-
directional impulse, 10
nsec rise time, fast tran
sient
Safety
Certified to DIN V VDE 0801
for Risk Class 5. Also designed
to meet UL 508 and CSA 22.2,
No. 142
-
M1981
Module Dimensions
Height:
Width:
Depth:
10.47" ( 266 mm)
2.38" ( 61 mm)
12.5" (318 mm)
Chassis Dimensions
Height:
Width:
Depth:
10.47" ( 266 mm)
19" ( 483 mm)