Instruction Manual
Trusted
TM
Communication Software Package T8017
Issue 10 Mar 08 PD-T8017 36
2.4.3. Data Summary
Output data summary
Controller 1 Controller 2 Controller 3
DATA rack dxpao dxpao dxpdo dxpdo
NETWORK_ID 1 1 1 1
TARGET_PEER_ID 2 3 4 5
SOURCE_DATA_ID 1 2 1 1
REFRESH_TMO 2000 2000 2000 2000
MIN_DELTA 20 20
Variable 1 - 16 Analogue
Data
Output
Analogue
Data Output
Digital Data
Output
Digital Data
Output
Table 14 Example 2 - Output Data Summary
Input data summary
Controller
1
Controller 2 Controller 3 Controller 4
DATA rack dxpdi dxpdi dxpai dxpai dxpdi dxpdi
NETWORK_ID 1 1 1 1 1 1
SOURCE_PEER 3* 3* 1 1 3* 2
SOURCE_DATA_ID 1 1 1 2 1 1
REFRESH_TMO 5000 5000 5000 5000 5000 5000
FS_VALUE FALSE FALSE -1024 -1024 FALSE FALSE
Variable 1 - 16 Boolean Data
Input
Boolean
Data Input
Analogue
Data Input
Analogue Data
Input
Boolean
Data Input
Boolean
Data Input
STATUS rack
Variable 1 Input data
valid
Input data
valid
Input data
valid
Input data valid Input data
valid
Input data
valid
Variable 2 - 9 Refreshed on
subnet 1…8
Refreshed
on subnet
1…8
Refreshed
on subnet
1…8
Refreshed on
subnet 1…8
Refreshed
on subnet
1…8
Refreshed
on subnet
1…8
CONTROL rack
Variable 1 Failure action Failure
action
Failure
action
Failure action Failure
action
Failure
action
Table 15 Example 2 - Input data summary
* Multi cast data receive from controller 3. The communication modules for network 1 on controllers 1,
2 and 4 must have the multicast IP address added to the communication module multicast address list;
refer to Multicast Configuration in PD-T8151B.