Instruction Manual

Trusted
TM
Communication Software Package T8017
Issue 10 Mar 08 PD-T8017 25
2.3.1. Controller 1 settings
Dual Peer to Peer Net Control, network 1 subnet 1.
dxpnc40 –
CONTROL rack
Value Comment
CHASSIS 1 Communication module located in chassis 1.
SLOT 7 Communication module is located in slot 7.
NETWORK_ID 1 Network 1
SUBNET_ID 1 Subnet 1
PEER_ID 1 Identity of this controller.
RESPONSE_TMO 0 Default
REFRESH_TMO 2000 Default
TX_DATA_TMO 500 Default
Variable 1 TRUE Enable Peer on this subnet.
Variable 2 FALSE This is a slave connection.
PEERS_1 rack
PEER_IP_01 10.10.1.1 Controller 1, network 1, subnet 1
PEER_IP_02 10.10.1.2 Controller 2, network 1, subnet 1
PEER_IP_03 10.10.1.3 Controller 3, network 1, subnet 1
PEER_IP_04 10.10.1.4 Controller 4, network 1, subnet 1
PEER_IP_05
PEER_IP_06
PEER_IP_07
Table 1 Example 1 - Controller 1 Net Control, network 1 subnet 1.