Relay Operation
The relays used on the T7446L contain SPDT contacts. For
the Form
-
A or Form
-
B selectable outputs, a jumper in the
module is used to select Form
-
A (N.O.) or Form
-
B (N.C.)
action.
The relays used on the T7446H contain t
wo SPST contacts
(one normally closed and one normally open). Jumpers within
the module are also used to select the relay form. On the
Form
-
C output, there is no guarantee for make
-
before
-
break
or break
-
before
-
make.
Output Form Selection
Two sets of jumper posts are used to select the output form for
the selectable relays. The jumper locations are shown in
Figure
4
. The jumper post designations are shown in Table
1
.
Only one jumper shunt can be installed for each relay. The
modules are shipped with the jumpers positioned for normally
open contact outputs.
Table
1
. Jumper Designations.
Jumper
Form
Description
E110
NO1
Selects normally open for relay 1
E111
NC1
Selects normally closed for relay 1
E120
NO2
Selects normally open for relay 2
E121
NC2
Selects normally closed for relay 2
E170
NO7
Selects normally open for relay 7
E171
NC7
Selects normally closed for relay 7
E180
NO8
Selects normally open for relay 8
E181
NC8
Selects normally
closed for relay 8