Owner's manual
Fire Detector Input Modules
(T7419)
PD
-
7032
Mar
-
06
19
Specifications
Safetybus Power
0.85 load units
Number of Inputs
16
Field Circuit Type
Standard 20 volt detector
loop, line monitored and
tested
Field Power
Voltage:
Current:
15 to 40 VDC
1.2 amps, maximum
Nominal Operating Voltage
Module provides regulated
23.5 Vdc for input loop
End of Line Terminator
3.0 Kohm resistor, typical
Quiescent Cu
rrent,
Maximum
3 to 10 mA, typical when
detector in normal state
Detector Alarm
See Load
-
line
characteristics, page
9
.
Reset
Voltage:
Current:
Time
:
<1 volt
<20
m
A
Programmable
Test Interval
15 seconds (typical)
Intrinsic Safety
External barrier
Over voltage Protection
27 volts continuous, 500
volts surge transient
Fusing
None (internal current limit
20 mA
—
no damage with
continual short circuit or
open input)
Isolation
2500 volts minimum (field
wiring
to control logic)
Operating Temperature
0°
to 60
°
C
(32
°
to 140
°
F)