6 (Issue 1) Industrial Control Services
Electromagnetic
Interference
• IEC 801 Part 2 - Electrostatic
Discharges
• IEC 801 Part 3 - Radiated
Electromagnetic Fields
• IEC 801 Part 4 - Transients
and Bursts
• IEC 801 Part 5 - Surge
Immunity
• ANSI/IEEE C37.90 - Surge
Withstand Capability
Level 3: Contact discharge of 6
kV
Level 3: 10 V/M, 27 MHz -
500 MHz
Level 4: 2 kV, 2.5 kHz for t =
60 sec
Level 3: 2 kV
2.5 kV damped 1 MHz sine
wave
4 kV bi-directional impulse, 10
nsec rise time, fast transient
Safety
Certified to DIN V VDE 0801
for Risk Class 5. Also designed
to meet UL 508 and CSA 22.2,
No. 142-M1981
Dimensions
Height:
Width:
Depth:
12.6" (320 mm)
1.27" (32 mm)
10.12" (257 mm)
Weight
3.0 lbs (1.4 kg)