User guide

Processor Modules (T7110, 11, 12, 20, 21, and 22)
14 (Issue 1) Industrial Control Services
Battery Type
Li/SO
2
Battery Life
Under Load:
Shelf Life:
6 months
10 years
I/O Interface
Cable Length:
I/O Chassis:
Triple redundant I/O
Safetybus
150 cable feet (45 m),
maximum
16 chassis, maximum
Operating Temperature
0° to 60° C
(32° to 140° F)
Storage Temperature
-40° to 85° C
(-40° to 185° F)
Operating Humidity
0 to 95% relative humidity,
non-condensing
Vibration
10 to 55 Hz:
±0.15mm
Shock
Operating:
15 g, ½ sine wave, 11 msec
Electromagnetic
Interference
IEC 801 Part 2 - Electrostatic
Discharges
IEC 801 Part 3 - Radiated
Electromagnetic Fields
IEC 801 Part 4 - Transients
and Bursts
IEC 801 Part 5 - Surge
Immunity
ANSI/IEEE C37.90 - Surge
Withstand Capability
Level 3: Contact discharge of 6
kV
Level 3: 10 V/M, 27 MHz -
500 MHz
Level 4: 2 kV, 2.5 kHz for t =
60 sec
Level 3: 2 kV
2.5 kV damped 1 MHz sine
wave
4 kV bi-directional impulse, 10
nsec rise time, fast transient
Safety
Designed to meet UL 508 and
CSA 22.2, No. 142-M1981
Dimensions
Height:
Width:
Depth:
12.6" (320 mm)
1.27" (32 mm)
10.125" (257 mm)