Instruction Manual

Configuration
8-32
T6200 – Analog Output Definition
-
Analog Output Block Editing:
Analog Output Parameter Adaptation: Verify all
AO parameters to make sure that they meet the
requirements of your application.
- The Channel number to which the analog output is connected to
- The Output signal type (1= 4-20 mA)
- The Output display indication, AO_Dis: 0= Direct indication (air to open); 1= Reverse
indication (air to close)
- The Lower bound (in percent) for the output, OPLOLM: Normally 0
- The Upper bound (in percent) for the output, OPHILM: Normally 100
- The max. Decreasing Rate (in % per sec), OPNR.M: Normally 100
- The max. Increasing Rate (in % per sec), OPPR.M: Normally 100
- The Recall of the old output value, Recall: 0= Start with zero; 1= Start at old value; 2=
Same as PID in this loop (default)
FIGURE 8-21
AO FB Configuration