User Manual
I/O Power Supply Modules
(T3510, 11, and 12)
2
Industrial Control Services
sharing circuit that receives power from all three I/O power
supply modules.
Should any I/O power supply module fail, only one leg of the
transceiver modules will lose power: the two remaining legs
will maintain proper operation of the Regent. In addition, all
the I/O modules will continue to operate properly by drawing
their current from the two remaining power supplies within
the I/O power supply assembly.
Figure
1
. I/O Power Distribution.
Input Power Regulation
A block diagram of a typical AC I/O power supply module is
shown in Figure
2
. A DC I/O power supply module is shown in
Figure
3
.