Owner's manual
Monitored Guarded Output Modules
(T3481/81A, 84, and 88/88A)
24
(Issue 2)
Industrial Control Services
Fusing
(front mounted)
One 3 amp, 250
V, fast acting
(3AB), rectifier
type, per output
Littelfuse 322
-
003
One 2 amp, 250
V, fast acting
(3AB), rectifier
type, per output
Littelfuse
322
-
002
One 2 amp, 250 V,
fast acting (3AB),
rectifier type, per
output
Littelfuse 322
-
002
Turn
-
On Delay
0.5 msec
0.5 msec
0.5 msec
Turn
-
Off Delay
0.5 msec
0.5 msec
0.5 msec
Output Test
Duration
250
m
sec for
single or dual
modules, max of
425
m
sec if switch
fault (dual
modules only)
250
m
sec for
single or dual
modules, max of
425
m
sec if
switch fault
(dual modules
only)
250
m
sec for single
o
r dual modules,
max of 425
m
sec if
switch fault (dual
modules only)
Heat Dissipation
30 Watts,
101
BTUs/hour
27 Watts,
92
BTUs/hour
27 Watts,
92
BTUs/hour
Over Voltage
Protection
70 VDC,
continuous
100 VDC,
5
seconds
275 VAC,
continuous
450 VAC,
5
seconds
275 VAC,
continuous
450 VAC, 5
seconds
Isolation
2500 volts minimum (field
wiring to control logic)
2500 volts minimum (output
group 1
-
8 to output group 9
-
16)
Operating Temperature
0°
to 60
°
C
(32
°
to 140
°
F)
Storage Temperature
-
40
°
to 85
°
C
(-
40
°
to 185
°
F)
Operating Humidity
0 to 95% relative humidity,
non
-
condensing
Vibration
10 to 55 Hz:
±0.15mm
Shock
Operating:
15 g, ½ sine wave, 11 msec