Manual
Isolated Guarded Digital Output Module
(T3485)
PD
-
6034
Mar
-
06
21
Surge Current
20 amps, 20 msec
Minimum Load
20 mA
Over Voltage Protection
Continuous:
450 VAC
Outp
ut Test Load Bump
Single module:
Dual modules:
None for turn
-
on test.
2
pulses at 125
m
sec each for
turn
-
off test or if single fault.
None during turn
-
on or turn
-
off test.
2 pulses at 125
m
sec each if
single fault.
Fusing
One 3 A, 250 V fast
-
acting
per output (Littelfuse 3AG
series)
Output Leakage
1 mA, maximum
Turn
-
On Delay
1.0 ms
Turn
-
Off Delay
1.0 ms
Heat Dissipation
25 Watts, 85 BTUs/hour
Isolation
250
0 volts minimum (field
wiring to control logic)
2500 volts minimum (output
to output)
Operating Temperature
0°
to 60
°
C
(32
°
to 140
°
F)
Storage Temperature
-
40
°
to 85
°
C
(-
40
°
to 185
°
F)
Operating Humidity
0 to 95% relative humidity,
non
-
condensing
Vibration
10 to 55 Hz:
±0.15mm
Shock
Operat
ing:
15 g, ½ sine wave, 11 msec