User guide
(T3444)
AC Digital Output Module
PD
-
6016
Mar
-
06
13
Specifications
Safetybus Power
0.8 load units
Number of Outputs
16 circuits divided into two
groups of 8 circuits each
Voltage Range
90 to 130 VAC
Frequency Range
47 to 63 Hz
Load Current
2
amps maximum per output
0°
to 50
°
C, derated linearly
to 1 amp at 60
°
C
8 amps maximum per group
of 8 outputs 0
°
to 60
°
C
16 amps maximum per
module 0
°
to 60
°
C
Minimum Load
50 mA
On State Drop
2.0 volts maximum
Surge Current
15 amps, 20 msec
Output Leakage
5 mA maximum
Fusing
One 3 A, 250 V, fast
-
acting
(3AG) per output, front panel
mounted
Turn
-
On Delay
½ AC cycle, maximum
Turn
-
Off Delay
½ AC cycle, maximum
Heat Dissipation
28 Watts, 97 BTUs/hour
Over voltage Protection
175 VAC, continuous
Isolation
2500 volts minimum (field
wiring to control logic)
2500 volts minimum (output
group 1
-
8 to output group 9
-
16)
Operating Temperature
0°
to 60
°
C
(32
°
to 140
°
F)
Storage Temperature
-
40
°
to 85
°
C
(-
40°
to 185
°
F)