Owner's manual
RTD Input Equipment
(T3432)
PD
-
6037
Mar
-
06
19
RTD Terminations
RTD wiring is connected to the scre
w terminals located at the
bottom of the termination panel as shown in Figure
16
. When
terminating RTD wiring, follow the recommendations listed
below.
1.
Greater accuracy is maintained with a heavier gauge RTD
lead wire. Lead wire resistance should not exceed
20
Ohms.
2.
All RTDs within a group of eight must be the same RTD
type (American or European) and use the same number of
leads (2, 3 or 4
-
wire). 2
-
wire and 4
-
wire RTDs can be mixed
in the same group.
3.
For unused RTD inpu
ts, short the +SENSE,
-
SENSE, and
-
FORCE terminals together.