Owner's manual

RTD Input Equipment
(T3432)
PD
-
6037
Mar
-
06
15
Table
1
. Temperature Data Ranges.
Out
-
of
-
Range Detection
When the RTD measures temperatures outside of the
operating range listed in Table
1
, the signal is considered to
be out
-
of
-
range. The RTD equipment will continue to provide
over
-
range and under
-
range readings up to the minimum and
maximum readings shown in the Table.
Also, many open
-
circuit and short
-
circuit wiring faults will
cause out
-
of
-
range conditions for RTD inputs. In these cases,
the temperature data value is the minimum or maximum
value shown in the Table.
When the signal is out
-
of
-
range, the NOSIG bit for the RTD
input is set. In application programming, the NOSIG contact
in ladder logic can be used to sense the RTD out
-
of
-
range
condition. For more information, see Programming, starting
on page
23
.
Installation Planning
Accuracy Considerations
Use the following guidelines to maximize overall system
accuracy: