posts as illustrated in Figure
11
to configure the type of
current sources installed on the termination panel.
Figure
11
. Selecting 1mA or 5mA Current Source.
Noise Filtering
RTDs and their associated wiring may be installed in
electrically noisy environments. Noise filtering is required to
ensure that this noise does not affect the re
ading of the low
level RTD signals. Jumper posts are located on the Mux to
select between 50 Hz or 60 Hz noise filtering.
Choose the frequency which represents the predominant
source of electrical noise in the RTD environment (e.g.
electrical motors). This configuration selection applies to all
16 RTD inputs. The jumper posts for noise filtering are
labeled “JP2”. Position the jumper on the posts as illustrated
in Figure
12
for noise filtering configuration.
Figure
12
. Selecting 50 or 60 Hz Noise Filtering.
RTD Data Format
The RTD input module provides linearized temperature data
to the processors in degrees Fahrenheit or Celsius. Jumper
posts are located on the Mux to select between degrees C or F.