User Manual

Thermocouple Input Assembly
(T3431)
PD
-
6024
Mar
-
06
27
Termination Panel Cable
Length
Maximum 50 cable feet
(15
m)
Isolation
2500 volts minimum (field
wiring to control logic)
Operating Temperature
0°
to 60
°
C
(32
°
to 140
°
F)
Storage Temperatu
re
-
40
°
to 85
°
C
(-
40
°
to 185
°
F)
Operating Humidity
0 to 95% relative humidity,
non
-
condensing
Safety
Certified to DIN V VDE
0801 (non
-
interfering) and
designed to meet UL 508 and
CSA 22.2, No. 142
-
M1981
Heat Dissipation
Input module:
Termination panel/Mux:
4.5 Watts, 15 BTUs/hour
2.5 Watts, 9 BTUs/hour
Dimensions
Input Module
Height:
Width:
Depth:
Termination Panel
He
ight:
Width:
Depth:
Mux
Height:
Width:
Depth:
12.6” (320 mm)
1.27” (32 mm)
10.125” (257 mm)
6.94” (176 mm)
19.0” (483 mm)
2.25” (57.2 mm)
4.5” (114 mm)
15.0” (381 mm)
1.25” (31.8 mm)
Weight
Input module:
Mux:
Termination
panel:
3.5 lbs (1.6 kg)
2 lbs (0.9 kg)
5.6 lbs (2.5 kg)