118 Publication 1783-UM003D-EN-E - December 2009
Chapter 4
In this field Select
Revision The major and minor revision of the switch.
Major revision: a number from 1...128.
Minor revision: a number from 1...255.
Electronic Keying • Compatible Module (default).
• Exact Match.
• Disable Keying.
Connection • Input Data (default): Allows input data connection only.
• Data: Allows input and output data connection.
Attention: This selection enables output tags, which can disable ports and interrupt connections to and
through the switch. You can disable a switch port by setting the corresponding bit in the output tag. The
output bits will be applied every time the switch receives the output data from the controller when the
controller is in Run mode. When the controller is in Program mode, the output bits are not applied.
The port is enabled if the corresponding output bit is 0. If you enable or disable a port by using the Device
Manager Web interface or the CLI, the port setting may be overridden by the output bits from the controller
on the next cyclic update of the I/O connection. The output bits will always take precedence, regardless of
whether the Device Manager Web interface or CLI was used to enable or disable the port.
Switch Base All selections are disabled. The switch base catalog number will be displayed based on the module you
selected.
Switch Expansion 1 The catalog number for the copper or fiber expansion modules you are using. Displayed for 14, 18, 22 and 26
port switches.
For 14 and 18 port switches, user selection of the expansion module is allowed.
For 22 and 26 port switches, Switch Expansion 1 will display 1783-MX08T. User selection of the expansion
module is not allowed.
Switch Expansion 2 The catalog number for the copper or fiber expansion modules you are using. Displayed only for 22 and 26
port switches. User selection of the expansion module is allowed.
Data Connection Password Enter the password for accessing the switch. Required for Data connection only.