User Manual Version 1.0 Owner manual

3-4
SP600 AC Drive User Manual
3.1.1.2 Input Power Conditioning
Certain events on the power system supplying a drive can cause
component damage or shortened product life. These conditions are
divided into two basic categories:
All Drives
The power system has power factor correction capacitors
switched in and out of the system either by the user or by the
power company.
The power source has intermittent voltage spikes in excess of
6000 volts. These spikes could be caused by other equipment on
the line or by events such as lightning strikes.
The power source has frequent interruptions.
Table 3.1 – MOV and Common Mode Capacitor Jumpers
Frame Jumper Removes
AN/A
B JP6-JP5 Common Mode Capacitors to Ground
C and D JP3B – JP3A Common Mode Capacitors to Ground
E JP3 – JP4 Common Mode Capacitors to Ground
DC+
DC–
Converter
Common
Mode
Capacitors
See Chart
Figure 3.2 – Phase-to-Ground MOV Removal
Jumper JP3-JP2 removes MOV to Ground (Frames A - D)
Jumper JP1-JP2 removes MOV to Ground (Frame E)
R
S
T
1234
Three-Phase
AC Input
See Chart