User Manual Version 1.0 Owner manual

Troubleshooting the Drive
13-17
13.5 Test Point Codes and Functions
Table 13.7 – Fault Names Cross-Referenced by Fault Number
No.
1
Fault No.
1
Fault No.
1
Fault
2 Function Loss 38 Phase U to Grnd 79 Excessive Load
3 Power Loss 39 Phase V to Grnd 80 AutoTune Aborted
4 UnderVoltage 40 Phase W to Grnd 81-86 Port 1-6 DPI Loss
5 OverVoltage 41 Phase UV Short 100 Parameter Chksum
7 Motor Overload 42 Phase VW Short 101 UserSet1 Chksum
8 Heatsink OvrTemp 43 Phase UW Short 102 UserSet2 Chksum
9 Trnsistr OvrTemp 48 Params Defaulted 103 UserSet3 Chksum
12 HW OverCurrent 63 Shear Pin 104 Pwr Brd Chksum1
13 Ground Fault 64 Drive Overload 105 Pwr Brd Chksum2
24 Decel Inhibit 69 DB Resistance 106 Incompat MCB-PB
25 OverSpeed Limit 70 Power Unit 107 Replaced MCB-PB
29 Analog In Loss 71-76 Port 1-6 Net Loss 108 Anlg Cal Chksum
33 Auto Rstrt Tries 77 IR Volts Range
36 SW OverCurrent 78 FluxAmpsRef Rang
1
Fault numbers not listed are reserved for future use.
Table 13.8 – Test Point Codes and Functions
Code Selected in
Testpoint x Sel (234, 236)
Function Whose Value is Displayed
in Testpoint x Data (235, 237)
1 DPI Error Status
2 Heatsink Temperature
3 Active Current Limit
4 Active PWM Frequency
5
Lifetime MegaWatt Hours
1
1
Use the equation below to calculate total Lifetime MegaWatt Hours.
6 Lifetime Run Time
7 Lifetime Powered Up Time
8 Lifetime Power Cycles
9
Life MegaWatt Hours Fraction
1
10
Life MegaWatt Hours Fraction Units
1
11-99 Reserved for Factory Use
Value of Code 9
Value of Code 10
---------------------------------
0.1×
Value of Code 5
+
Total Lifetime MegaWatt Hours
=